7.4.4. Filter Change AMP900 and AMP1200
NB: When changing filters, the unit must be switched
off (press function button for at least 2 seconds),
disconnected from the mains and prevented from
being switched on.
• Open the unit front cover (AMP900) / remove side
panels and extraction panel (AMP1200).
• Remove the filter retaining plate and pull the old
filters out of their holders.
• Clean the inside of the unit and supply air duct,
check component condition and cleanliness as far
as possible. Clean the components if necessary.
• Insert new filters with the correct direction of flow
in the filter holder. (The arrow on the side of new
M5/F7 filters shows flow direction. The arrow must
point into the unit).
• Fit the retaining panels and service cover/panels.
• Close the front cover (AMP900) / mount side panels
and extraction panel (AMP1200).
• Reconnect to the mains and start the unit.
• Reset service. See “Reset Service” on page 28.