3.2.5. Holiday Mode - Activation
Holiday mode is used as basic ventilation when the room
is unused for an extended period, e.g. holidays.
In holiday mode, Airmaster will run the unit with min. air flow.
The internal control system function “Low temperature” is
active to protect the unit against ice formation. The control
function is able to activate the heating surfaces if necessary.
The internal control system function “High temperature” is
deactivated in holiday mode.
See also “Internal Control System Functions” on pages 25
and 26.
Activate
holiday mode.
Press holiday mode button (pos. 5. under ”Control Elements”
on page 6) for 2 seconds.
>> The unit will go into holiday mode.
Cancel
holiday mode:
Press the function button (pos. 2. under ”Control Elements”
on page 6).
>> The unit will return to automatic operation.
3.3.
Warning and Alarm
The Airlinq control system monitors temperatures, air-
flow, cooling module function, filter status and various
components.
In the event of a fault, the control panel will show an amber
or red symbol. The unit will maintain operation for amber
warnings as best it can, whilst it will stop for red alarms.
Warnings and alarms are shown by flashes at various inter-
vals or a constant light. In the event of multiple faults, the
faults will be shown with a brief pause in between each one.
Warning and alarm displays (yellow and red):
Light signals for warnings and alarms:
1. Slow flash (2 seconds on 2 seconds off).
2. Rapid flash (0.5 seconds on, 0.5 seconds off).
3. Rapid double flash (0.5 seconds on, 0.5 seconds off,
0.5 seconds on) at 2 second intervals.
4. Light on constantly.
See explanation of fault types on next page.