background image

Air Flow Balancing

10

The following is a method of field balancing a HRV/ERV using
a Pitot tube advantageous in situations when flow stations are not
installed in the ductwork. Procedure should be performed with the
HRV/ERV on normal speed.

The first step is to operate all mechanical systems on most desire
speed, which have an influence on the ventilation system, i.e.the
forced air furnace or air handler if applicable. This will provide the
maximum pressure that the HRV/ERV  will need to overcome, and
allow for a more accurate balancing of the unit.

Drill a small hole in the duct (about 3/16"), three feet downstream
of any elbows or bends, and one foot upstream of any elbows or bends.
These are recommended distances but the actual installation may limit
the amount of straight duct.

The Pitot tube should be connected to a magnehelic gauge capable
of reading from 0 to 0.25 in. (0-62 Pa) or other digital airflow meter.
The tube coming out of the top of the pitot is connected to the
high pressure side of the gauge/meter and the tube coming out of the
side of the pitot is connected to the low pressure or reference side
of the gauge/meter.

Insert the pitot tube into the duct; pointing the tip into the airflow, as shown in option #1. For general balancing,
it is sufficient to move the pitot tube around in the duct and take an average or typical reading. Repeat this
procedure in the other duct. Determine which duct has the highest airflow (highest reading on the gauge).
Then slower down that motor speed by adjusting dial/speed controller on control board to match the lower
reading from the other duct. The flows should now be balanced. Actual airflow can be determined from the
gauge/metre reading. The value read on the gauge is called the velocity pressure and on the flow meter is
called air velocity(FPM). The Pitot tube comes with a chart that will give the air flow velocity based on the
velocity pressure indicated by the gauge. This velocity will be in either feet per minute or metres per second.
To determine the actual airflow, the velocity is multiplied by the cross sectional area of the duct being measured.

MAGNEHELIC

0

.1

.2

.3

.4

.5

Duct

AIR

FLOW

Pitot
tube

High
Pressure
Tap

Low
Pressure Tap

Magnehelic

gauge

Pitot tube and gauge
(Option #1)

NOTE:

Place the magnehelic gauge on a
level surface and adjust it to zero.

Balancing Procedure

All the HRV/ERV’s components are in place and functioning properly.
All sealing of the ductwork system has been completed.
Set the unit to normal speed.
Air flows in branch to specific areas of the house should be adjusted first prior to balancing  the unit.
After taking reading of both stale air and fresh air, the duct with the lower CFM reading should be left alone
while the duct with the higher airflow should be slower down to match the lower reading by adjusting
dial/speed controller on control board (see Fig.1).
Return unit to appropriate fan speed for normal operation.

Prior to balancing, ensure that:

1.
2.
3.
4.
5.

6.
7.   Follow step-5 to balance the flow in high speed.

It is required to have balanced air flows in a HRV/ERV. The volume of air brought in from the outside
must equal the volume of air exhausted by the unit while running at normal speed. If the air flows are
not properly balanced, then:

• The HRV/ERV may not function at its maximum efficiency
• A negative or positive air pressure may occur in the house
• The unit may not defrost properly

Low

High

Low

High

Supply

Fan Speed

Exhaust

Fan Speed

(Fig. 1)

Temp. Sensor

Note:

To reduce the air flow turn the Knob

counter clockwise as shown in Fig.1

,

Pitot Tube Airflow Balancing (Method 1)

Summary of Contents for Softaire RERV-80

Page 1: ...RTIFIED Compact Unit model RHRV C100A Aluminum Core RHRV C100P Polypropylene Core RERV C100 Enthalpy Core RHRV 80 P RERV 80 Field balancing Ports HRV ERV INSTALLATION AND OPERATION INSTRUCTIONS 4 Pine Street Toronto ON Canada M9N 2Y8 Tel 416 247 0045 Fax 416 247 2012 www ontarioheatingltd com info ontarioheatingltd com Rev 3 0 DT 18 12 04 ...

Page 2: ...ed by the manufacturer 8 When performing installation servicing or cleaning these unit it is suggested to wear safety glasses and gloves 9 Do not use this unit for commercial purpose 10 For residential use only The unit must be grounded 11 Do not install in a cooking area 12 This unit is not designed to exhaust combustion and or dilution air for fuel burning appliances CAUTION 1 Turn the unit OFF ...

Page 3: ...rd Bracket Door Hinges Mounting Brackets T Connector Webbing Brackets Ladder Locks Chains Springs Brackets Drain Pipe 1 1 2 2 n a 1 n a 1 1 2 2 2 2 1 1 2 2 1 1 1 1 1 1 1 1 2 2 1 Set 1 Set 4 4 1 1 2 Sets 2 Sets 1 Set 1 Set 1 1 16 18 17 20 12 13 14 15 10 11 9 8 7 6 5 4 3 2 1 Filter 6 1 2 x 10 MERV 4 2 2 19 Motorized damper spring return 120V 1 1 22 Motorized Damper Spring return Built in by Factory ...

Page 4: ...y Switch Main control Board Main Control Board Bracket Door Hinges Mounting Brackets T Connector Webbing Brackets Ladder Locks Chains Springs Brackets Drain Pipe 9315 014043C 9312 9313 9314 9326 014043 9319 9320 9321 014016 9322 9355 9328 011135 9330 9332 9354 9331 1 1 1 2 2 2 1 n a n a n a 1 n a n a n a 1 1 1 1 2 2 2 2 2 2 1 1 1 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 1 Set 1 Set 1 Set 4 4 4 1 1 1 2 ...

Page 5: ...y Exhaust Adjustable Door Latch Drain Spout Assembly Core Locking Bracket Core Locking Nut Safety Switch Main control Board Main Control Board Bracket Door Hinges Mounting Brackets T Connector Webbing Brackets Ladder Locks Chains Springs Brackets Drain Pipe 1 2 1 1 2 2 1 2 1 1 1 1 2 1 Set 4 1 2 Sets 1 Set 1 16 18 17 20 12 13 14 15 10 11 9 8 7 6 5 4 3 2 1 Filter 10 x 12 MERV 4 Filter 8 x 12 MERV 4 ...

Page 6: ...RED YEL GND C 5 DAT RED YEL GND RED YEL GND Note Same power source can be used for wall switch Time delay switch TC100 120 TC100 120P and HRV ERV TC100 120P TC100 120 RED BLACK WHITE Ground 120 Vac 1 60Hz Power Supply TC100 5V Important Note When installing timers or time delay switches make sure that they are for appropriate HRV ERV models Damper Motor Single winding Option 1 External Damper Moto...

Page 7: ...hermostat and thereby turning on the cooling system If you identify this type of thermostat you must use the Alternate Interlock Wiring For a furnace connected to a cooling system Wiring Diagram cont d 5 Furnace Fan Coil Heat Pump Interlock Standard Interlock Wiring W R G Y W R G Y C FOUR WIRE TWO WIRE heating only Cooling System THERMOSTAT TERMINALS TWO WIRE W A R N I N G Never connect a 120 volt...

Page 8: ...c NOTE 5 ft 3 ft 6 Highly Recommended Highly Recommended ...

Page 9: ...e vent DVS 100 c w Side Exhaust Intake hood Re circulation Efficiency 98 Double vent DVV 100C c w Vertical Exhaust Intake hood Note All Exhaust Vents must be installed min 5 ft away from sidewalls Re circulation Efficiency If distance X is 5ft 99 7 X is 3ft 96 5 Re circulation Efficiency 98 Fully Ducted System Motorized spring return backdraft damper Recommended HRV with Fan Coil System Motorized ...

Page 10: ...ows one person installation for vertical and horizontal installation VERTICAL Note After installation make sure the HRV ERV is properly leveled If not levelled correctly then defrost will not perform effectively and or unit may frost in winter Note UP UP PULL DOWN Strap jtant ay 01 2 8 11 NOT SUPPLIED jtantay 12 23 11 Vibration Spring Washer Screw CHAIN MOUNTING SYSTEM optional Available for both ...

Page 11: ...tical installation T Connector I D Drain Pipe Zip Tie Drain Spout to Drain Drain Pan P Trap Drain Pan Drain Spout Assembly Rubber washer Drain Spout Nut Steel washer HRV ERV Steel Housing Plastic Drain Pan Lid HRV and ERV Typical Installations cont d Typical Installations of Single Vents Access door For vertical installation Use this drain for horizontal installation Fresh air intake and exhaust d...

Page 12: ... reading The value read on the gauge is called the velocity pressure and on the flow meter is called air velocity FPM The Pitot tube comes with a chart that will give the air flow velocity based on the velocity pressure indicated by the gauge This velocity will be in either feet per minute or metres per second To determine the actual airflow the velocity is multiplied by the cross sectional area o...

Page 13: ...om the holes CFM Opening Cross sectionalArea sq ft x velocity FPM Ø5 0 010 50 0 012 60 0 016 70 0 022 80 0 027 90 0 034 100 0 041 110 0 048 120 0 057 130 P CFM P Velocity Pressure in inch 2 2 3 3 MAGNEHELIC 0 1 2 3 4 5 Remove plug while balancing Remove plug while balancing 1 4 11 Plugs Pitot Tube Air Flow Balancing cont d Field Air flow Balancing Method 2 Balancing Table Differen al Pressure the C...

Page 14: ...ain Pipe Inspect drain tube drain pipe and P trap for blockage mold or kinks Flush with warm soapy water and replace if worn bent or unable to clean 4 Clean Duct Work if Required Wipe and vacuum the duct once every year The duct work running to and from HRV ERV may accumulate dirt You may wish to contact a heating ventilation company to do this ATTENTION Do not use cleaning solution for the HRV ER...

Page 15: ...imer switch blinks Control board reports error lost communication with main control board refer to problem 4 check all wire connections on timer switch and main control board 7 LED s on the Main Control board and the remote wall mount Timer Switch will flash 0 5 second On then 2 seconds Off then repeat the cycle Exhaust fan open circuit a motor burned b fan overheated replace motor call technician...

Page 16: ...14 Rev 3 0 DT 18 12 04 b y A i r S p e c i a l i t i e s 4 Pine Street Toronto ON Canada M9N 2Y8 Tel 416 247 0045 Fax 416 247 2012 www ontarioheatingltd com info ontarioheatingltd com ...

Reviews: