14SEER AIR COOLING ONLY SYSTEM TECHNICAL MANUAL
15
7. The Specification of Wiring
Note:
The cross-section areas of wires or lines should not be less than the corresponding ones listed
in the table below; Besides, if the power wires are quite long from the unit, please choose the
windings with larger cross-section area to guarantee the normal power supply.
Model
Type
Indoor power wires
Thermostat communication wires
Outdoor power
wires
Indoor
Outdoor
18 K series
(
single phase
)
Cooling only
3*16Awg
3*18Awg
2*18Awg
3*16Awg
24 K series
(
single phase
)
Cooling only
3*18Awg
2*18Awg
3*14Awg
30 K series
(
single phase
)
Cooling only
3*18Awg
2*18Awg
36 K series
(
single phase
)
Cooling only
3*18Awg
2*18Awg
42 K series
(
single phase
)
Cooling only
3*18Awg
2*18Awg
3*12Awg
48 K series
(
single phase
)
Cooling only
3*18Awg
2*18Awg
60 K series
(
single phase
)
Cooling only
3*18Awg
2*18Awg