14SEER AIR COOLING ONLY SYSTEM TECHNICAL MANUAL
31
4. Insulation Work
4.1 Insulation material and thickness
4.1.1. Insulation material
158
°F
in the high-pressure side, no less than 248
°F
in the low-pressure side (For the cooling type machine,
no requirements at the low-pressure side.)
◆
Example: Heat pump type----Heat-resistant Polyethylene foam (withstand above 248
°F
)
Cooling only type----Polyethylene foam (withstand above 212
°F
)
4.1.2. Thickness choice for insulation material
Insulation material thickness is as follows:
Pipe diameter (in)
Adiabatic material thickness
Refrigerant pipe
0.25—1
0.39in
1.13—1.5
0.59in
Drainage pipe
Inner diameter 0.79—1.26
0.24in
4.2 Refrigerant pipe insulation
4.2.1. Work Procedure
①
Before laying the pipes, the non-jointing parts and non-connection parts should be heat insulated.
②
When the gas proof test is eligible, the jointing area, expanding area and the flange area should be heat
insulated.
4.2.2. Insulation for non-jointing parts and non-connection parts
wrong
right
Gas pipe and liquid pipe should
not be put together to insulate
Insulate the gas pipe
(cooling only)
Insulate the gas pipe and
liquid pipe