R410A 17.5 SEER Inverter Split System Technical Manual
1. Precaution on Installation
1.1. Measure the necessary length of the connecting pipe and make it by the following way.
a.
Connect the indoor unit at first, then the outdoor unit.
Bend the tubing in proper way. Do not harm them.
CAUTIONS:
⚫
Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds
⚫
With hands before fastening the flare nuts.
Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
Pipe gauge
Tightening torque
Flare dimension A
Min (in) Max
Flare shape
¼
11.07
~
11.80lbf.ft
5/16
3/8
3/8
18.45
~
19.18lbf.ft
7/16
½
½
25.83
~
26.56lbf.ft
9/16
5/8
5/8
33.21
~
34.68lbf.ft
11/16
3/4
¾
47.97
~
49.44lbf.ft
13/16
7/8
b.
The stop value of the outdoor unit should be closed absolutely (as original state). Every time you connect
it, first loosen the nuts at the part of stop value, then connect the flare pipe immediately (in 5 minutes).
If the nuts have been loosened for a long time, dusts and other impurities may enter the pipe system
and may cause malfunction later. So please expel the air out of the pipe with refrigerant before
connection.
c.
Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten
the nuts at the repair-points.
1.2. Locate The Pipe
a.
Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the
wall conduit and its cover.
b.
Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will
cause water leakage by condensation.
c.
Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation
to do no damage to the tubing.
1.3. Connect the pipes.
1.4. Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting
the indoor unit with the outdoor unit in fluent flow.
1.5. Be sure of no leakage by checking it with leak detector or soap water.
1.6. Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath
(fittings) and bind it well with the tapes to prevent leakage.
Summary of Contents for ACTH2418VG1-D
Page 1: ...R410A Inverter Split System 17 5 SEER Technical Manual January 2021 Version A TM 18SS 01...
Page 4: ...R410A 17 5 SEER Inverter Split System Technical Manual 1 Nomenclature 1 1 Indoor unit...
Page 5: ...R410A 17 5 SEER Inverter Split System Technical Manual 1 2 Outdoor unit...
Page 22: ...R410A 17 5 SEER Inverter Split System Technical Manual 4 Service Space...