Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze-ups and
may block the terminations.
IMPORTANT
NOTE:
All horizontal runs of exhaust pipe must slope back toward
unit. A minimum of 1/4” (6 mm) drop for each 12” (305 mm) of
horizontal run is mandatory for drainage.
NOTE:
Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE
:
Exhaust piping should be checked carefully to make sure
there are no sages or low spots.
EXHAUST PIPE
Horizontal Application
Figure 20
Use the following steps to correctly size vent pipe diameter.
Table 4
*Any approved termination may be added to the minimum length
listed.
MINIMUM VENT PIPE LENGTHS