Technical Data
Ecodesign - DCC (RQ)
Notes Units
DCC057DR-10NYV0
DCC044DR-12LXX0
DCC044DR-12KSS0
DCC046DR-12KSQ0
SEPR
1, 3, 5
5.61
6.19
7.04
6.93
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
758156.53
522817.39
464924.03
486651.94
Rated Refrigerant Capacity P
A
1, 3, 5
kW
573.60
436.70
441.50
455.40
Rated Power Input D
A
kW
195.77
130.36
131.40
136.35
Rated EER
DC,A
2.93
3.35
3.36
3.34
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
629.7 / 524.6
479.5 / 401.5
484.2 / 410.2
498.0 / 423.9
Declared Power Input D
B
kW
159.7 / 128.7
106.2 / 87.3
107.2 / 88.2
110.9 / 91.9
Declared EER
DC,B
3.94 / 4.08
4.51 / 4.60
4.52 / 4.65
4.49 / 4.61
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
564.9 / 458.7
435.0 / 350.6
443.4 / 361.9
455.7 / 324.9
Declared Power Input D
C
kW
106.2 / 83.3
72.3 / 56.6
70.4 / 55.7
72.6 / 50.2
Declared EER
DC,C
5.32 / 5.51
6.02 / 6.20
6.30 / 6.50
6.28 / 6.47
Declared Refrigerant Capacity
P
D
kW
475.4 / 353.3
358.7 / 269.0
386.6 / 292.6
484.5 / 344.6
Declared Power Input D
D
kW
71.3 / 52.8
50.3 / 38.0
41.7 / 31.4
52.5 / 37.9
Declared EER
DC,D
6.66 / 6.70
7.13 / 7.07
9.27 / 9.33
9.23 / 9.08
SSCEE
2, 3, 5
%
172
190
202
199
SSCEE Tier
Tier 1 (2018)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
574.20
437.30
442.00
455.90
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
573.60
436.70
441.50
455.40
Declared EER
d
35°C
2.93
3.35
3.36
3.34
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
629.7 / 524.6
479.5 / 401.5
484.2 / 410.2
498.0 / 423.9
Declared EER
d
30°C
3.94 / 4.08
4.51 / 4.60
4.52 / 4.65
4.49 / 4.61
Declared Cooling Capacity
25°C Pdc
kW
564.9 / 458.7
435.0 / 350.6
443.4 / 361.9
455.7 / 324.9
Declared EER
d
25°C
5.32 / 5.51
6.02 / 6.20
6.30 / 6.50
6.28 / 6.47
Declared Cooling Capacity
20°C Pdc
kW
475.4 / 353.3
358.7 / 269.0
386.6 / 292.6
484.5 / 344.6
Declared EER
d
20°C
6.66 / 6.70
7.13 / 7.07
9.27 / 9.33
9.23 / 9.08
Sound Power Level L
dB(A)
91.03
86.74
93.64
95.57
Air fl ow rate
m³/h
232965.67
279558.81
279558.81
279558.81
Off mode P
OFF
0.14
0.14
0.08
0.08
Thermostat-off mode P
TO
2.40
1.94
2.18
2.35
Standby Mode P
SB
0.26
0.27
0.15
0.15
Crankcase heater mode P
CK
0.00
0.00
0.13
0.11
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
111
Chillers
DeltaChill
TM
DeltaChill Technical Manual 9758541 V1.1_06_2020