Technical Data
Ecodesign - DCC (XQ)
Notes Units
DCC035DX-08KRR0
DCC033DX-10KLR0
DCC036DX-10KRR0
DCC043DX-10LXX0
SEPR
1, 3, 5
6.79
7.35
7.18
6.07
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
383986.83
331892.81
373673.23
520152.51
Rated Refrigerant Capacity P
A
1, 3, 5
kW
351.90
329.20
361.90
426.10
Rated Power Input D
A
kW
113.52
96.82
109.01
133.57
Rated EER
DC,A
3.10
3.40
3.32
3.19
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
332.6 / 275.9
361.9 / 302.7
338.7 / 278.6
472.1 / 396.6
Declared Power Input D
B
kW
76.3 / 59.5
78.7 / 63.0
73.3 / 57.5
109.0 / 89.5
Declared EER
DC,B
4.36 / 4.64
4.60 / 4.81
4.62 / 4.84
4.33 / 4.43
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
360.8 / 297.6
327.2 / 256.3
366.8 / 300.2
431.3 / 348.1
Declared Power Input D
C
kW
60.9 / 47.7
49.7 / 37.8
57.8 / 45.7
74.2 / 57.9
Declared EER
DC,C
5.92 / 6.23
6.59 / 6.77
6.34 / 6.57
5.81 / 6.02
Declared Refrigerant Capacity
P
D
kW
318.4 / 241.5
271.8 / 180.2
320.2 / 242.4
359.2 / 269.2
Declared Power Input D
D
kW
35.2 / 26.2
27.5 / 18.8
33.1 / 24.9
50.5 / 38.1
Declared EER
DC,D
9.05 / 9.23
9.87 / 9.58
9.67 / 9.75
7.12 / 7.07
SSCEE
2, 3, 5
%
197
202
205
186
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
352.30
329.60
362.30
426.60
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
351.90
329.20
361.90
426.10
Declared EER
d
35°C
3.10
3.40
3.32
3.19
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
332.6 / 275.9
361.9 / 302.7
338.7 / 278.6
472.1 / 396.6
Declared EER
d
30°C
4.36 / 4.64
4.60 / 4.81
4.62 / 4.84
4.33 / 4.43
Declared Cooling Capacity
25°C Pdc
kW
360.8 / 297.6
327.2 / 256.3
366.8 / 300.2
431.3 / 348.1
Declared EER
d
25°C
5.92 / 6.23
6.59 / 6.77
6.34 / 6.57
5.81 / 6.02
Declared Cooling Capacity
20°C Pdc
kW
318.4 / 241.5
271.8 / 180.2
320.2 / 242.4
359.2 / 269.2
Declared EER
d
20°C
9.05 / 9.23
9.87 / 9.58
9.67 / 9.75
7.12 / 7.07
Sound Power Level L
dB(A)
85.57
85.56
85.74
86.25
Air fl ow rate
m³/h
115364.31
144205.38
144205.38
160142.32
Off mode P
OFF
0.08
0.08
0.08
0.14
Thermostat-off mode P
TO
1.42
1.34
1.47
1.85
Standby Mode P
SB
0.13
0.14
0.14
0.26
Crankcase heater mode P
CK
0.13
0.11
0.13
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Technical Data
Ecodesign - DCC (XQ)
Notes Units
DCC026DX-06KKL0
DCC022DX-08JJK0
DCC027DX-08KKL0
DCC032DX-08KLR0
SEPR
1, 3, 5
6.61
7.35
7.11
6.99
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
291582.25
213294.97
280664.96
340196.14
Rated Refrigerant Capacity P
A
1, 3, 5
kW
260.10
211.60
269.30
321.00
Rated Power Input D
A
kW
82.83
60.46
78.74
100.00
Rated EER
DC,A
3.14
3.50
3.42
3.21
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
287.7 / 217.3
232.0 / 169.9
296.4 / 221.8
354.5 / 298.6
Declared Power Input D
B
kW
67.8 / 48.0
48.6 / 33.7
64.3 / 45.9
81.8 / 65.1
Declared EER
DC,B
4.25 / 4.53
4.77 / 5.04
4.61 / 4.83
4.33 / 4.59
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
234.9 / 166.2
251.1 / 182.7
239.2 / 167.9
323.4 / 253.2
Declared Power Input D
C
kW
38.7 / 26.5
37.9 / 26.6
36.6 / 25.3
51.8 / 39.4
Declared EER
DC,C
6.08 / 6.28
6.63 / 6.86
6.54 / 6.63
6.24 / 6.43
Declared Refrigerant Capacity
P
D
kW
251.8 / 177.0
194.7 / 138.9
254.6 / 178.5
271.3 / 179.7
Declared Power Input D
D
kW
29.0 / 20.7
20.3 / 14.9
26.9 / 19.6
28.9 / 19.5
Declared EER
DC,D
8.67 / 8.55
9.60 / 9.31
9.48 / 9.12
9.38 / 9.21
SSCEE
2, 3, 5
%
190
208
200
194
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
260.40
211.90
269.60
321.40
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
260.10
211.60
269.30
321.00
Declared EER
d
35°C
3.14
3.50
3.42
3.21
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
287.7 / 217.3
232.0 / 169.9
296.4 / 221.8
354.5 / 298.6
Declared EER
d
30°C
4.25 / 4.53
4.77 / 5.04
4.61 / 4.83
4.33 / 4.59
Declared Cooling Capacity
25°C Pdc
kW
234.9 / 166.2
251.1 / 182.7
239.2 / 167.9
323.4 / 253.2
Declared EER
d
25°C
6.08 / 6.28
6.63 / 6.86
6.54 / 6.63
6.24 / 6.43
Declared Cooling Capacity
20°C Pdc
kW
251.8 / 177.0
194.7 / 138.9
254.6 / 178.5
271.3 / 179.7
Declared EER
d
20°C
8.67 / 8.55
9.60 / 9.31
9.48 / 9.12
9.38 / 9.21
Sound Power Level L
dB(A)
84.48
82.59
84.70
85.39
Air fl ow rate
m³/h
86523.23
115364.31
115364.31
115364.31
Off mode P
OFF
0.08
0.08
0.08
0.08
Thermostat-off mode P
TO
0.90
0.82
0.96
1.21
Standby Mode P
SB
0.12
0.13
0.13
0.13
Crankcase heater mode P
CK
0.09
0.09
0.09
0.11
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
120
Chillers
DeltaChill
TM
DeltaChill Technical Manual 9758541 V1.1_06_2020