Technical Data
Ecodesign - DCC (XQ)
Notes Units
DCC045DX-12KSQ0
DCC048DX-1
1NXY0
DCC055DX-12NYY0
DCC057DX-12NYV0
SEPR
1, 3, 5
6.93
5.94
5.90
5.77
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
480386.37
600139.03
692624.02
728006.83
Rated Refrigerant Capacity P
A
1, 3, 5
kW
449.40
481.20
551.60
566.90
Rated Power Input D
A
kW
135.36
154.23
177.36
188.97
Rated EER
DC,A
3.32
3.12
3.11
3.00
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
421.8 / 303.8
532.4 / 437.3
610.4 / 513.4
628.6 / 526.8
Declared Power Input D
B
kW
91.7 / 62.0
126.0 / 100.1
145.3 / 119.1
153.6 / 124.2
Declared EER
DC,B
4.60 / 4.90
4.23 / 4.37
4.20 / 4.31
4.09 / 4.24
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
454.0 / 324.8
474.0 / 391.5
556.9 / 450.1
568.6 / 462.0
Declared Power Input D
C
kW
72.5 / 50.2
82.8 / 66.5
98.7 / 77.0
102.6 / 80.9
Declared EER
DC,C
6.26 / 6.48
5.72 / 5.89
5.64 / 5.85
5.54 / 5.71
Declared Refrigerant Capacity
P
D
kW
483.0 / 344.6
402.9 / 290.3
464.2 / 348.0
475.4 / 353.2
Declared Power Input D
D
kW
52.6 / 37.9
58.0 / 41.5
67.1 / 50.5
70.5 / 52.3
Declared EER
DC,D
9.18 / 9.10
6.94 / 6.99
6.91 / 6.89
6.74 / 6.75
SSCEE
2, 3, 5
%
199
186
183
178
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
449.90
481.60
552.10
567.40
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
449.40
481.20
551.60
566.90
Declared EER
d
35°C
3.32
3.12
3.11
3.00
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
421.8 / 303.8
532.4 / 437.3
610.4 / 513.4
628.6 / 526.8
Declared EER
d
30°C
4.60 / 4.90
4.23 / 4.37
4.20 / 4.31
4.09 / 4.24
Declared Cooling Capacity
25°C Pdc
kW
454.0 / 324.8
474.0 / 391.5
556.9 / 450.1
568.6 / 462.0
Declared EER
d
25°C
6.26 / 6.48
5.72 / 5.89
5.64 / 5.85
5.54 / 5.71
Declared Cooling Capacity
20°C Pdc
kW
483.0 / 344.6
402.9 / 290.3
464.2 / 348.0
475.4 / 353.2
Declared EER
d
20°C
9.18 / 9.10
6.94 / 6.99
6.91 / 6.89
6.74 / 6.75
Sound Power Level L
dB(A)
87.45
86.23
86.22
87.26
Air fl ow rate
m³/h
173046.46
176156.55
192170.78
192170.78
Off mode P
OFF
0.08
0.14
0.14
0.14
Thermostat-off mode P
TO
2.27
1.34
1.94
2.30
Standby Mode P
SB
0.15
0.27
0.27
0.27
Crankcase heater mode P
CK
0.11
0.00
0.00
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
122
Chillers
DeltaChill
TM
DeltaChill Technical Manual 9758541 V1.1_06_2020