Technical Data
Ecodesign - DCF (RQ)
Notes Units
DCF036DR-08KLR0
DCF039DR-08KRR0
DCF045DR-08LXX0
DCF036DR-10KLR0
SEPR
1, 3, 5
7.02
6.82
6.11
7.22
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
345763.98
389374.50
506613.61
340846.51
Rated Refrigerant Capacity P
A
1, 3, 5
kW
327.80
358.30
418.10
332.10
Rated Power Input D
A
kW
103.41
117.09
143.68
100.03
Rated EER
DC,A
3.17
3.06
2.91
3.32
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
360.3 / 300.4
393.8 / 333.9
460.0 / 385.9
364.6 / 303.7
Declared Power Input D
B
kW
85.1 / 67.8
96.7 / 79.5
117.5 / 96.2
81.6 / 65.3
Declared EER
DC,B
4.23 / 4.43
4.07 / 4.20
3.91 / 4.01
4.47 / 4.65
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
325.2 / 254.7
361.8 / 295.6
418.1 / 337.9
328.5 / 257.0
Declared Power Input D
C
kW
54.5 / 41.6
64.0 / 50.5
79.7 / 62.0
51.9 / 39.7
Declared EER
DC,C
5.97 / 6.13
5.65 / 5.85
5.24 / 5.45
6.33 / 6.48
Declared Refrigerant Capacity
P
D
kW
261.7 / 179.9
286.0 / 240.7
333.8 / 264.9
265.1 / 180.5
Declared Power Input D
D
kW
25.7 / 21.2
28.2 / 28.7
39.5 / 39.7
26.5 / 20.2
Declared EER
DC,D
10.19 / 8.50
10.15 / 8.40
8.45 / 6.67
10.02 / 8.95
SSCEE
2, 3, 5
%
181
180
164
190
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 1 (2018)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
328.30
358.90
418.80
332.60
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
327.80
358.30
418.10
332.10
Declared EER
d
35°C
3.17
3.06
2.91
3.32
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
360.3 / 300.4
393.8 / 333.9
460.0 / 385.9
364.6 / 303.7
Declared EER
d
30°C
4.23 / 4.43
4.07 / 4.20
3.91 / 4.01
4.47 / 4.65
Declared Cooling Capacity
25°C Pdc
kW
325.2 / 254.7
361.8 / 295.6
418.1 / 337.9
328.5 / 257.0
Declared EER
d
25°C
5.97 / 6.13
5.65 / 5.85
5.24 / 5.45
6.33 / 6.48
Declared Cooling Capacity
20°C Pdc
kW
261.7 / 179.9
286.0 / 240.7
333.8 / 264.9
265.1 / 180.5
Declared EER
d
20°C
10.19 / 8.50
10.15 / 8.40
8.45 / 6.67
10.02 / 8.95
Sound Power Level L
dB(A)
86.89
87.57
89.27
86.09
Air fl ow rate
m³/h
170362.44
170362.44
170362.44
212953.05
Off mode P
OFF
0.08
0.08
0.14
0.08
Thermostat-off mode P
TO
2.19
2.71
2.88
2.10
Standby Mode P
SB
0.13
0.13
0.25
0.14
Crankcase heater mode P
CK
0.11
0.13
0.00
0.11
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.
Ec
od
esi
gn
132
Chillers
DeltaChill
TM
DeltaChill Technical Manual 9758541 V1.1_06_2020