Technical Data
Ecodesign - DCF (XQ)
Notes Units
DCF101TX-18R
VWW
DCF096TX-21R
YVV
DCF098TX-21R
VVV
DCF101TX-21R
VVW
SEPR
1, 3, 5
6.43
6.69
6.76
6.66
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
1103325.21
988126.24
1014750.02
1063380.41
Rated Refrigerant Capacity P
A
1, 3, 5
kW
957.80
891.90
926.00
955.20
Rated Power Input D
A
kW
342.07
288.64
299.68
314.21
Rated EER
DC,A
2.80
3.09
3.09
3.04
Declared Refrigerant Capacity
P
B
1, 3, 5
kW
958.3 / 848.3
881.7 / 775.4
919.2 / 811.2
945.1 / 837.1
Declared Power Input D
B
kW
242.5 / 206.0
206.4 / 177.4
214.8 / 185.7
222.2 / 193.1
Declared EER
DC,B
3.95 / 4.12
4.27 / 4.37
4.28 / 4.37
4.25 / 4.34
Declared Refrigerant Capacity
P
C
1, 3, 5
kW
926.2 / 811.6
834.9 / 723.8
874.3 / 754.8
905.9 / 786.5
Declared Power Input D
C
kW
170.5 / 145.5
147.3 / 125.8
153.8 / 129.9
159.9 / 136.0
Declared EER
DC,C
5.43 / 5.58
5.67 / 5.75
5.68 / 5.81
5.66 / 5.78
Declared Refrigerant Capacity
P
D
kW
765.3 / 702.8
712.7 / 617.7
740.0 / 648.0
763.3 / 666.3
Declared Power Input D
D
kW
82.0 / 103.2
73.9 / 92.3
75.2 / 95.5
80.2 / 97.7
Declared EER
DC,D
9.33 / 6.81
9.65 / 6.69
9.84 / 6.79
9.51 / 6.82
SSCEE
2, 3, 5
%
168
171
177
175
SSCEE Tier
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2, 4, 5
kW
958.60
892.80
926.80
956.10
Declared Cooling Capacity
35°C Pdc
2, 3, 5
kW
957.80
891.90
926.00
955.20
Declared EER
d
35°C
2.80
3.09
3.09
3.04
Declared Cooling Capacity
30°C Pdc
2, 3, 5
kW
958.3 / 848.3
881.7 / 775.4
919.2 / 811.2
945.1 / 837.1
Declared EER
d
30°C
3.95 / 4.12
4.27 / 4.37
4.28 / 4.37
4.25 / 4.34
Declared Cooling Capacity
25°C Pdc
kW
926.2 / 811.6
834.9 / 723.8
874.3 / 754.8
905.9 / 786.5
Declared EER
d
25°C
5.43 / 5.58
5.67 / 5.75
5.68 / 5.81
5.66 / 5.78
Declared Cooling Capacity
20°C Pdc
kW
765.3 / 702.8
712.7 / 617.7
740.0 / 648.0
763.3 / 666.3
Declared EER
d
20°C
9.33 / 6.81
9.65 / 6.69
9.84 / 6.79
9.51 / 6.82
Sound Power Level L
dB(A)
90.68
89.46
89.99
90.40
Air fl ow rate
m³/h
259040.95
302214.45
302214.45
302214.45
Off mode P
OFF
0.15
0.15
0.15
0.15
Thermostat-off mode P
TO
6.35
5.79
5.51
5.93
Standby Mode P
SB
0.35
0.36
0.36
0.36
Crankcase heater mode P
CK
0.00
0.00
0.00
0.00
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside confi guration.
(6) Please contact Airedale regarding Non Compliant selections.