Te
ch
nic
al
Chillers
DeltaChill™ Air Cooled and FreeCool
121
Chiller Technical Manual 7267818 V1.13.0_01_2018
Fre
eC
oo
l
ELECTRICAL DATA
46
47
48
Unit Data
DCF088TR-19HYYV
DCF090TR-20HYVV
DCF095TR-21HVVV
Nominal Run Amps
(1)
A
551.3
579.6
608.0
Maximum Start Amps
A
818.7
847.0
875.4
Recommended Mains Fuse Size
A
630
630
630
Evaporator
Immersion Heater Rating
W
250
250
250
Condenser Fan - Per Fan (EC)
Quantity
19
20
21
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
47.9 / 47.9 / 55.2
47.9 / 55.2 / 55.2
55.2 / 55.2 / 55.2
Quantity
3 + 3 + 3
3 + 3 + 3
3 + 3 + 3
Motor Rating
kW
29.8 / 29.8 / 33.1
29.8 / 33.1 / 33.1
33.1 / 33.1 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 326 / 326
326 / 326 / 326
326 / 326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
522.0
543.2
564.4
Reactive power reduction/saving
(4) kVAr
54.1
65.3
76.6
Maximum Start Amps
A
789.4
810.6
831.8
Recommended Mains Fuse Size
A
630
630
630
Electronic Soft-start
Nominal Run Amps
A
551.3
579.6
608.0
Maximum Start Amps
A
688.3
716.6
745.0
Recommended Mains Fuse
A
630
630
630
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
522.0
543.2
564.4
Maximum Start Amps
A
659.0
680.2
701.4
Recommended Mains Fuse Size
A
630.0
630.0
630.0
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
28.5
28.5
28.5
Unit Nominal Run Amps
A
579.6
607.9
636.4
Recommended Mains Fuse Size
A
630
630
670
Motor Rating
kW
16.4
16.4
16.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
35.0
35.0
35.0
Unit Nominal Run Amps
A
586.1
614.4
642.9
Recommended Mains Fuse Size
A
630
670
670
Motor Rating
kW
20.3
20.3
20.3
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
26.9
26.9
26.9
Unit Nominal Run Amps
A
573.2
601.2
629.5
Recommended Mains Fuse Size
A
630
630
670
Motor Rating
kW
16.8
16.8
16.8
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
33.2
33.2
33.2
Unit Nominal Run Amps
A
578.4
606.3
634.5
Recommended Mains Fuse Size
A
630
630
670
Motor Rating
kW
20.7
20.7
20.7
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data - Regular Quiet