DeltaChill™ Air Cooled and FreeCool
125
Chiller Technical Manual 7267818 V1.13.0_01_2018
Fre
eC
oo
l
ELECTRICAL DATA
58
59
60
Unit Data
DCF053DX-12DPV0
DCF055DX-11DYV0
DCF055DX-12DYY0
Nominal Run Amps
(1)
A
347.1
369.2
348.9
Maximum Start Amps
A
610.5
636.6
624.5
Recommended Mains Fuse Size
A
400
400
400
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (EC)
Quantity
12
11
12
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 55.2
47.9 / 55.2
47.9 / 47.9
Quantity
2 + 3
3 + 3
3 + 3
Motor Rating
kW
36.2 / 33.1
29.8 / 33.1
29.8 / 29.8
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 326
326 / 326
326 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
324.0
347.3
333.8
Reactive power reduction/saving
(4) kVAr
41.2
39.8
28.6
Maximum Start Amps
A
587.4
614.7
609.4
Recommended Mains Fuse Size
A
400
400
400
Electronic Soft-start
Nominal Run Amps
A
347.1
369.2
348.9
Maximum Start Amps
A
480.1
506.2
494.1
Recommended Mains Fuse
A
400
400
400
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
324.0
347.3
333.8
Maximum Start Amps
A
457.0
484.3
479.0
Recommended Mains Fuse Size
A
400
400
400
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
14.8
21.2
14.8
Unit Nominal Run Amps
A
361.8
390.2
363.5
Recommended Mains Fuse Size
A
400
450
400
Motor Rating
kW
8.4
12.1
8.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
21.2
28.5
21.2
Unit Nominal Run Amps
A
368.2
397.5
369.8
Recommended Mains Fuse Size
A
400
450
400
Motor Rating
kW
12.1
16.4
12.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
13.9
19.8
13.9
Unit Nominal Run Amps
A
358.2
385.3
360.3
Recommended Mains Fuse Size
A
400
450
400
Motor Rating
kW
8.6
12.4
8.6
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
19.8
26.9
19.8
Unit Nominal Run Amps
A
363.1
391.0
365.2
Recommended Mains Fuse Size
A
400
450
400
Motor Rating
kW
12.4
16.8
12.4
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.
DCF Electrical Data Extra Quiet