Chiller Technical Manual 7267818 V1.13.0_01_2018
A
ir C
oo
led
Ambient (°C)
Model
Supply
Temp
°C
25°C
30°C
35°C
40°C
Output
Input
Output
Input
Output
Input
Output
Input
kW
kW
kW
kW
kW
kW
kW
kW
130
DCC074TR-17GPYY
5
757.9
194.4
722.9
214.5
683.6
237.4
639.7
262.9
6
780.4
195.7
744.6
215.9
704.0
238.7
659.4
264.3
7
803.2
197.1
766.7
217.2
724.9
240.0
679.5
265.8
8
826.4
198.5
789.1
218.6
746.6
241.5
700.0
267.2
9
849.7
199.9
811.7
220.0
767.9
242.8
720.7
268.7
10
873.3
201.3
834.6
221.5
790.2
244.3
741.9
270.2
131
DCC079TR-18GYYY
5
817.9
209.3
779.7
230.8
736.9
255.2
689.4
282.3
6
842.4
210.8
803.3
232.3
758.5
256.4
710.8
283.8
7
867.4
212.3
827.4
233.8
781.6
257.9
732.6
285.4
8
892.7
213.8
851.8
235.3
805.0
259.5
754.8
287.0
9
918.3
215.4
876.5
236.9
828.7
261.1
777.3
288.6
10
944.2
217.0
901.5
238.4
852.9
262.7
800.3
290.2
132
DCC082TR-17GYVV
5
847.7
221.1
807.5
244.0
763.2
270.5
714.2
300.2
6
873.3
222.7
832.8
245.8
786.8
272.1
736.3
301.8
7
899.3
224.4
857.8
247.4
810.7
273.8
758.8
303.3
8
925.4
226.0
882.6
248.9
835.1
275.4
781.6
304.9
9
951.9
227.7
908.3
250.6
859.7
277.1
804.9
306.5
10
978.7
229.4
934.4
252.4
884.8
278.9
828.5
308.2
133
DCC085TR-18GVVV
5
868.6
223.5
826.7
246.7
781.4
273.9
731.0
304.5
6
894.8
225.0
853.1
248.6
805.7
275.5
754.0
306.1
7
921.2
226.6
878.7
250.2
830.3
277.1
777.3
307.7
8
948.1
228.2
903.9
251.6
855.3
278.8
801.1
309.4
9
975.3
229.9
930.3
253.3
880.6
280.5
825.3
311.1
10
1002.7
231.6
957.1
255.0
906.3
282.2
849.9
312.8
134
DCC088TR-18GVVW
5
910.2
236.0
866.8
260.6
818.1
288.8
764.7
320.5
6
937.4
237.6
892.8
262.2
843.4
290.5
788.3
322.2
7
965.3
239.4
919.7
263.9
869.2
292.3
812.4
323.9
8
993.7
241.2
947.7
265.9
895.4
294.1
837.0
325.6
9
1022.3
243.1
974.9
267.6
922.0
296.0
861.9
327.3
10
1051.4
244.9
1003.0
269.5
949.0
297.9
887.3
329.1
135
DCC091TR-18GVWW
5
942.7
248.0
898.1
273.7
848.1
303.2
792.8
336.2
6
970.3
249.6
924.9
275.4
874.1
305.0
816.8
337.8
7
998.9
251.5
952.6
277.3
900.5
306.9
841.2
339.5
8
1027.9
253.4
980.8
279.3
927.3
308.9
866.0
341.2
9
1057.2
255.4
1008.9
281.2
954.5
310.8
891.1
343.0
10
1086.8
257.4
1037.6
283.2
982.1
312.9
916.7
344.8
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (comp fans).
3
Duties applicable for chilled water ∆T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x ∆T)
6
For conditions outside of those quoted please refer to Airedale.
DCC Performance Data EC Fans