Te
ch
ni
ca
l
Chillers
DeltaChill™ Air Cooled and FreeCool
190
Chiller Technical Manual 7267818 V1.13.0_01_2018
A
ir C
oo
led
110
111
112
Unit Data
DCC058DR-12DVV0
DCC060DR-12DVW0
DCC063DR-12DWW0
Nominal Run Amps
(1)
A
397.6
409.7
421.8
Maximum Start Amps
A
665.0
673.1
657.2
Recommended Mains Fuse Size
A
450
450
450
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (EC)
Quantity
12
12
12
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
55.2 / 55.2
55.2 / 59.2
59.2 / 59.2
Quantity
3 + 3
3 + 3
3 + 3
Motor Rating
kW
33.1 / 33.1
33.1 / 36.2
36.2 / 36.2
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
326 / 326
326 / 298
298 / 298
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
368.5
382.1
395.8
Reactive power reduction/saving
(4)
kVAr
51.0
48.9
46.8
Maximum Start Amps
A
635.9
645.5
631.2
Recommended Mains Fuse Size
A
450
450
450
Electronic Soft-start
Nominal Run Amps
A
397.6
409.7
421.8
Maximum Start Amps
A
534.6
542.7
538.0
Recommended Mains Fuse
A
450
450
450
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
368.5
382.1
395.8
Maximum Start Amps
A
505.5
515.1
512.0
Recommended Mains Fuse Size
A
450
450
450
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
8.9
11.2
11.2
Unit Nominal Run Amps
A
406.2
420.8
432.9
Recommended Mains Fuse Size
A
450
450
450
Motor Rating
kW
4.4
6.2
6.2
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
11.2
14.8
14.8
Unit Nominal Run Amps
A
408.7
424.4
436.5
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
6.1
8.4
8.4
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
7.3
10.2
10.2
Unit Nominal Run Amps
A
403.4
417.9
430.1
Recommended Mains Fuse Size
A
450
450
450
Motor Rating
kW
4.5
6.4
6.4
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
10.1
13.9
13.9
Unit Nominal Run Amps
A
405.7
420.8
433.0
Recommended Mains Fuse Size
A
450
450
500
Motor Rating
kW
6.3
8.6
8.6
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Regular Quiet