ELECTRICAL DATA
143
144
145
Unit Data
DCC048DX-10EPV0
DCC049DX-10EYY0
DCC049DX-12EPV0
Nominal Run Amps
(1)
A
339.4
341.1
347.1
Maximum Start Amps
A
602.8
616.7
610.5
Recommended Mains Fuse Size
A
400
355
400
Evaporator
Immersion Heater Rating
W
170
170
170
Condenser Fan - Per Fan (EC)
Quantity
10
10
12
Full Load Amps
A
3.9
3.9
3.9
Motor Rating
kW
2.6
2.6
2.6
Compressor - Per Compressor
Nominal Run Amps
A
59.2 / 55.2
47.9 / 47.9
59.2 / 55.2
Quantity
2 + 3
3 + 3
2 + 3
Motor Rating
kW
36.2 / 33.1
29.8 / 29.8
36.2 / 33.1
Sump Heater Rating
W
140
140
140
Start Amps
(2)
A
298 / 326
326 / 326
298 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98)
(3)
Nominal Run Amps
A
316.2
326.1
324.0
Reactive power reduction/saving
(4)
kVAr
41.1
28.5
41.2
Maximum Start Amps
A
579.6
601.7
587.4
Recommended Mains Fuse Size
A
400
355
400
Electronic Soft-start
Nominal Run Amps
A
339.4
341.1
347.1
Maximum Start Amps
A
472.4
486.3
480.1
Recommended Mains Fuse
A
400
355
400
Power Factor Correction (PF
0.98) & Electronic Soft Start
(3)
Nominal Run Amps
A
316.2
326.1
324.0
Maximum Start Amps
A
449.2
471.3
457.0
Recommended Mains Fuse Size
A
400
355
400
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
8.9
8.9
8.9
Unit Nominal Run Amps
A
347.9
349.5
355.6
Recommended Mains Fuse Size
A
400
400
400
Motor Rating
kW
4.4
4.4
4.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps
A
11.2
11.2
11.2
Unit Nominal Run Amps
A
350.4
352.1
358.1
Recommended Mains Fuse Size
A
400
400
400
Motor Rating
kW
6.1
6.1
6.1
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
7.3
7.3
7.3
Unit Nominal Run Amps
A
345.2
347.1
352.9
Recommended Mains Fuse Size
A
400
400
400
Motor Rating
kW
4.5
4.5
4.5
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps
A
10.1
10.1
10.1
Unit Nominal Run Amps
A
347.5
349.4
355.2
Recommended Mains Fuse Size
A
400
400
400
Motor Rating
kW
6.3
6.3
6.3
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold
DCC Electrical Data - Extra Quiet