Notes: Units DCF075TR-16GPPY DCF080TR-17GPYY DCF085TR-18GYYY
SEPR
1,3,5
6.13
6.12
6.02
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
828430
894134
961577
Rated Refrigerant Capacity
P
A
1,3,5 kW
685.9
738.3
781.2
Rated Power Input D
A
kW
232.5
252.0
270.3
Rated EER
DC,A
2.95
2.93
2.89
Declared Refrigerant Capacity P
B
1,3,5 kW
673.7 / 578.5
730.7 / 637.3
777.8 / 684.4
Declared Power Input D
B
kW
165.7 / 141.3
181.7 / 154.9
196.8 / 170.0
Declared EER
DC,B
4.07 / 4.09
4.02 / 4.11
3.95 / 4.03
Declared Refrigerant Capacity P
C
1,3,5 kW
628.0 / 501.8
691.9 / 587.2
741.9 / 641.0
Declared Power Input D
C
kW
118.3 / 92.0
129.7 / 109.3
142.4 / 119.8
Declared EER
DC,C
5.31 / 5.45
5.33 / 5.37
5.21 / 5.35
Declared Refrigerant Capacity P
D
1,3,5 kW
544.6 / 525.6
585.7 / 504.5
619.4 / 558.0
Declared Power Input D
D
kW
64.0 / 80.6
69.2 / 78.5
74.9 / 86.9
Declared EER
DC,D
8.52 / 6.52
8.46 / 6.42
8.27 / 6.42
SSCEE
2,3,5
%
162.3
162.5
159.1
SSCEE Tier
6
Tier 1 (2018)
Tier 1 (2018)
Not Compliant
Rated Cooling Capacity P
rated,c
2,4,5
690
743.3
n/a
Declared Cooling Capacity 35°C Pdc 2,3,5 kW
685.9
738.3
n/a
Declared EER
d
35°C
2.95
2.93
n/a
Declared Cooling Capacity 30°C Pdc 2,3,5 kW
673.7 / 578.5
730.7 / 637.3
n/a
Declared EER
d
30°C
4.07 / 4.09
4.02 / 4.11
n/a
Declared Cooling Capacity 25°C Pdc 2,3,5 kW
628.0 / 501.8
691.9 / 587.2
n/a
Declared EER
d
25°C
5.31 / 5.45
5.33 / 5.37
n/a
Declared Cooling Capacity 20°C Pdc 2,3,5 kW
544.6 / 525.6
585.7 / 504.5
n/a
Declared EER
d
20°C
8.52 / 6.52
8.46 / 6.42
n/a
Sound Power Level LWA
dB(A)
93
93
n/a
Air flow rate
m³/h
338572
359733
n/a
Off mode P
OFF
kW
0.169
0.169
n/a
Thermostat-off mode P
TO
kW
4.670
5.688
n/a
Standby Mode P
SB
kW
0.335
0.351
n/a
Crankcase heater mode P
CK
kW
0.000
0.000
n/a
Technical Data
Ecodesign
DCF075TR-16GPPY, DCF080TR-17GPYY, DCF085TR-18GYYY
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
Chillers
DeltaChill™ Air Cooled and FreeCool
Introduction
281
Chiller Technical Manual 7267818 V1.13.0_01_2018
Te
ch
nic
al