Technical - Direct Expansion
Performance Data - Tandem Compressor (X2)
Full Load (X2)
Ambient (°C)
Unit
Air On DB / RH
25
30
35
40
46
LIR6042U-X240-0
25°C / 42%
Gross Total Cooling (kW)
27.62
27.62
26.66
25.51
26.53
Power Input (kW)
7.29
7.29
7.97
8.81
11.51
EER
3.79
3.79
3.34
2.89
2.30
30°C / 32%
Gross Total Cooling (kW)
38.23
39.06
37.62
39.29
38.88
Power Input (kW)
9.49
11.34
12.54
16.01
20.70
EER
4.03
3.44
3.00
2.45
1.88
35°C / 24%
Gross Total Cooling (kW)
47.69
46.39
46.76
45.02
42.82
Power Input (kW)
12.16
13.33
17.07
18.81
20.97
EER
3.92
3.48
2.74
2.39
2.04
40°C / 18%
Gross Total Cooling (kW)
54.42
52.89
51.26
47.68
43.65
Power Input (kW)
14.11
15.69
17.37
18.77
20.61
EER
3.85
3.37
2.95
2.54
2.12
LIR6042U-X250-0
25°C / 42%
Gross Total Cooling (kW)
32.02
32.02
31.01
29.69
31.65
Power Input (kW)
9.18
9.18
9.89
10.83
15.63
EER
3.49
3.49
3.14
2.74
2.02
30°C / 32%
Gross Total Cooling (kW)
45.98
45.41
45.95
44.19
41.92
Power Input (kW)
12.97
13.46
16.98
18.67
20.81
EER
3.55
3.37
2.71
2.37
2.01
35°C / 24%
Gross Total Cooling (kW)
53.52
52.45
50.75
48.48
43.71
Power Input (kW)
14.55
15.58
17.20
18.61
20.08
EER
3.68
3.37
2.95
2.61
2.18
40°C / 18%
Gross Total Cooling (kW)
58.46
55.55
52.13
48.54
44.52
Power Input (kW)
14.18
15.15
16.45
17.83
15.57
EER
4.13
3.67
3.17
2.72
2.86
LogiCool InRak™
IT Cooling
24 InRak™ Technical Manual 7462807 V1.11.0_04_2016
Te
ch
ni
ca
l
DX
Note: The shaded area indicate that the Compressor speed is modulated to achieve dew point control.
All the performance data is based on a SHR of 1.0.
Maximum duty data is based on achievable duty at maximum air volume
Performance data is based upon a unit with no filtration.