Technical Data - Dual Circuit Chilled Water
Electrical Data - (CC)
LIR6042U-CC22
LIR6042U-CC26
LIR6042U-CC30
LIR6042U-CC40
Standard Outdoor Unit Match -
Chiller
Chiller
Chiller
Chiller
Unit Data Cooling only
Nominal Run Amps
(1)
A
1.3
2.4
2.9
4.4
Maximum Start Amps
A
2.4
2.4
4.4
4.4
Recommended Mains Fuse Size
(3)
A
10
10
10
10
Max Mains Incoming Cable Size
mm²
10
10
10
10
Mains Supply 50Hz (-0)
V
400V / 3PH + N / 50Hz
400V / 3PH + N / 50Hz
Mains Supply 60Hz (-1)
V
380V / 3PH + N / 60Hz
380V / 3PH + N / 60Hz
Control Circuit
VAC
24
24
24
24
Evaporator Fan - Motor - Per Fan
Motor Type
EC
EC
EC
EC
Quantity x Motor Size
(2)
kW
4 x 0.15
4 x 0.15
4 x 0.5
4 x 0.5
Full Load Amps
A
1.2
1.2
2.2
2.2
Locked Rotor Amps
A
N/A
N/A
N/A
N/A
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
Variable
Variable
Variable
Variable
Number of Elements
3
3
3
3
Rating (Total)
kW
10.5
10.5
10.5
10.5
Current Per Phase (50Hz Supply)
A
15.2
15.2
15.2
15.2
Current Per Phase (60Hz Supply)
A
16.0
16.0
16.0
16.0
IT Cooling
LogiCool InRak™
49
InRak™ Technical Manual 7462807 V1.11.0_04_2016
Te
ch
nic
al
Du
al C
irc
uit
(C
C)
(1) Values given for Cooling Only unit .
(2) Stated motor power is based on maximum electrical power absorbed.
(3) Values may change based on additional selections (i.e. Heating).