Precision Air Conditioning
SmartCool
TM
– D
Precision Air Conditioning
135
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Electrical Data – W2F0 Continued
SC25D067-W2F0-0
SC25D073-W2F0-0
SC25D080-W2F0-0
Standard Dry Cooler Match
1 x DR95
1 x DR95
1 x DR95
(EC)
Unit Data Full Function - W2F0
Nominal Run Amps
(1)
A
87.3
88.7
96.4
Maximum Start Amps
A
231.1
226.1
268.9
Recommended Mains Fuse Size
A
100
100
125
Max Mains Incoming Cable Size
mm²
35
35
35
Mains Supply
V
400V / 3PH + N / 50Hz
Control circuit
VAC
24
24
24
Unit Data Cooling Only- W2F0
Nominal Run Amps
A
61.5
64.4
75.9
Maximum Start Amps
A
205.3
201.8
248.4
Recommended Mains Fuse Size
A
80
80
100
Evaporator Fan Motor - Per Fan
Motor Type
AC
AC
AC
Quantity x Motor Size
(2)
kW
3 x 2.38
3 x 2.38
3 x 2.38
Full Load Amps
A
5
5
5
Locked Rotor Amps
A
17.5
17.5
17.5
Compressor 1 , Circuit 1
Motor Size
(3)
kW
10.86
12.15
13.73
Nominal Run Amps
A
19.2
20.7
24.5
Locked Rotor Amps
A
163
158
197
Type of Start
Direct On Line
Compressor 2, Circuit 1
Motor Size
(3)
kW
10.86
12.15
13.73
Nominal Run Amps
A
19.2
20.7
24.5
Locked Rotor Amps
A
163
158
197
Type of Start
Direct On Line
Standard Dry Cooler Match - Motor Per Fan
AC
AC
EC
Quantity x Motor Size
kW
4 x 0.88
4 x 0.88
4 x 1.68
Full Load Amps
A
1.65
1.65
2.6
OPTIONAL EXTRAS
Electric Heating
Number of stage of Reheat
3
3
3
Number of Elements
9
9
9
Rating (Total)
kW
31.5
31.5
31.5
Current Per Phase
A
45.47
45.47
45.47
Humidifier
Capacity
kg/hr
15
15
15
Rating
kW
11.25
11.25
11.25
Full Load Amps
A
16.2
16.2
16.2
First upgrade Fan Motor - EC Motor - Per Fan
Quantity x Motor Size
(2)
kW
3 x 2.2
3 x 2.2
3 x 2.2
Full Load Amps
A
3.3
3.3
3.3
Locked Rotor Amps
A
3.3
3.3
3.3
Second upgrade Motor - EC Motor - Per Fan
Quantity x Motor Size
(2)
kW
3 x 3.1
3 x 3.1
3 x 3.1
Full Load Amps
A
4.8
4.8
4.8
Locked Rotor Amps
A
4.8
4.8
4.8
Standard Dry Cooler Match - EC Motor-Per Fan
Quantity x Motor Size
(2)
kW
4 x 1.68
4 x 1.68
N/A
Full Load Amps
A
2.6
2.6
N/A
Dry Cooler Match - SCAF Fan
Quantity x Motor Size
(2)
kW
4 x 1.94
4 x 1.94
4 x 1.94
Full Load Amps
A
3.4
3.4
3.4
(1) Values given for function units with standard selections for heating, humidification, supply air fans 7°C evaporating and 54.4°C condensing.
(2) Stated motor power is based on maximum electrical power absorbed
(3) Values are per compressor
W
2