Precision Air Conditioning
SmartCool
TM
– D
Precision Air Conditioning
155
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Mechanical Data - C0C0 Continued
SC31D055-C0C0-0
SC31D065-C0C0-0
SC31D075-C0C0-0
Capacity
(1)
Nom Cooling (Gross)
kW
79.1
87.0
94.6
Fan Gain
kW
1.25
2.06
3.22
Dimensions
- H x D x W
mm
3113 x 890 x 1980
3113 x 890 x 1980
3113 x 890 x 1980
Weight
- Machine / Operating
kg
1010 / 1100
1010 / 1100
1010 / 1100
Construction
Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black Grey (RAL 7021)
Material/Colour
Frame:Anodised Aluminium Frame with Black Nylon Corners
Cooling Coil
Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages
1 (Modulated) / 1
Water volume
L
87.9
87.9
87.9
Water flow rate
l/s
3.79
4.27
4.71
Pressure drop
kPa
33.13
36.25
39.40
Fan & Motor
Backwards Curved, Centrifugal direct drive
Motor Type
EC
EC
EC
Quantity x Motor Size
kW
3 x 3.1
3 x 3.1
3 x 3.1
Speed @25Pa ESP/ Maximum ESP
Rpm
1061 / 1520
1261 / 1520
1479 / 1520
Maximum ESP
Pa
528
330
77
Nominal Airflow
m³/s
5.8
6.9
7.9
Connections
Water Inlet / Outlet
mm
42
42
42
Condensate Drain Hose
mm
22
22
22
Filtration
Disposable to BS EN 779-G4-741
Quantity
4
4
4
OPTIONAL EXTRAS
Electric Heating (Total)
kW
31.5
31.5
31.5
Humidifier
Capacity
kg/hr
15
15
15
Feed/Drain
¾" BSPF Braided flexible hose / 19mm hose connection
Condensate Pump
Head
m
10
10
10
Flow
l/m
5
5
5
Drain
10mm Stainless Steel Stub Connection
Standard Fan Motor - EC Motor
Backwards Curved, Centrifugal direct drive
Quantity x Motor Size
kW
N/A
N/A
N/A
Speed @ 25Pa / Maximum ESP
rpm
N/A
N/A
N/A
Maximum ESP
Pa
N/A
N/A
N/A
Fan Gain
kW
N/A
N/A
N/A
Larger Fan Motor - EC Motor
Backwards Curved, Centrifugal direct drive
Quantity x Motor Size
kW
N/A
N/A
N/A
Speed @ 25Pa / Maximum ESP
rpm
N/A
N/A
N/A
Maximum ESP
Pa
N/A
N/A
N/A
Fan Gain
kW
N/A
N/A
N/A
Low Pressure Hot Water
(2)
Capacity Gross
kW
39.8
42.7
45.2
Water Flow (Nominal)
l/s
0.81
0.88
0.95
Pressure drop
Kpa
35.9
37.4
38.8
LPHW Connection Sizes
mm
22
22
22
(1) Entering air 24°C/ 45% RH water 7°C/ 12°C
(2) Based upon low pressure hot water 82°C inlet/71°C outlet. Air on 20°C
(3) Fan gain based on 25Pa ESP @ nominal air volume. Fan gain figure will change as airflow and ESP change.