Electrical Data – X2X2 Continued
SCD31D100-X2X2
SC31D120-X2X2
SC31D130-X2X2
Standard Condenser Match -
2 x CR80
2 x CR105
2 x CR105
Unit Data - X2X2
(1)
Nominal Run Amps
A
100.1
108.2
112.8
Maximum Start Amps
A
213.1
221.3
256.5
Recommended Mains Fuse Size
A
125
125
125
Max Mains Incoming Cable Size
mm²
70
70
70
Mains Supply
V
400V / 3PH + N / 50Hz
Control circuit
VAC
24
24
24
Unit Data Cooling Only – X2X2
Nominal Run Amps
A
83.9
92.0
96.6
Maximum Start Amps
A
196.9
205.1
240.3
Recommended Mains Fuse Size
A
100
125
125
Evaporator Fan - Motor - Per Fan
Motor Type
EC
EC
EC
Quantity x Motor Size
(2)
kW
3 x 3.1
3 x 3.1
3 x 3.1
Full Load Amps
A
4.8
4.8
4.8
Locked Rotor Amps
A
4.8
4.8
4.8
Compressor 1 , Circuit 1 & 2
(3)
Motor Size
kW
7.19
9.46
9.46
Nominal Run Amps
A
12.87
16.93
16.93
Locked Rotor Amps
A
92
130
130
Type of Start
Direct On Line
Compressor 2, Circuit 1 & 2
(3)
Motor Size
kW
9.46
9.46
10.86
Nominal Run Amps
A
16.93
16.93
19.22
Locked Rotor Amps
A
130
130
163
Type of Start
Direct On Line
Standard Condenser Match - AC Motor Per Fan
Quantity x Motor Size
kW
3 x 0.6
3 x 0.6
3 x 0.6
Full Load Amps
A
2.62
2.62
2.62
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
3
3
3
Number of Elements
9
9
9
Rating (Total)
kW
31.5
31.5
31.5
Current Per Phase
A
45.47
45.47
45.47
Humidifier
Capacity
kg/hr
15
15
15
Rating
kW
11.25
11.25
11.25
Full Load Amps
A
16.2
16.2
16.2
Standard Size Fan Motor - EC Motor - Per Fan
Quantity x Motor Size
kW
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
N/A
Larger Size Motor - EC Motor - Per Fan
Quantity x Motor Size
kW
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
N/A
Standard Condenser Match - EC Motor-Per Fan
Quantity x Motor Size
kW
3 x 0.73
3 x 0.73
3 x 0.73
Full Load Amps
A
3.3
3.3
3.3
SCAF Condenser Match - Motor-Per Fan
Quantity x Motor Size
kW
3 x 1.4
3 x 1.4
3 x 1.4
Full Load Amps
A
6
6
6
(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed
(3) Values are per compressor
X