SmartCool
TM
- D
Precision Air Conditioning
84
Precision Air Conditioning
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Electrical Data –X2C0
SC19D033-X2C0-0
SC19D038-X2C0-0
SC19D045-X2C0-0
Standard Condenser Match
1 x CR50
1 x CR65
1 x CR65
Unit Data Full function - X2C0
Nominal Run Amps
A
51.7
54.5
56.4
Maximum Start Amps
A
113.2
130.2
143.2
Recommended Mains Fuse Size
A
63
63
63
Max Mains Incoming Cable Size
mm²
35
35
35
Mains Supply
V
400V / 3PH + N / 50Hz
Control circuit
VAC
24
24
24
Unit Data Cooling only –X2C0
Nominal Run Amps
A
29.8
35.6
39.4
Maximum Start Amps
A
91.3
111.2
126.1
Recommended Mains Fuse Size
A
40
40
50
Evaporator Fan Motor - Per Fan
Motor Type
EC
EC
EC
Quantity x Motor Size
kW
2 x 2.2
2 x 2.2
2 x 2.2
Full Load Amps
A
3.3
3.3
3.3
Locked Rotor Amps
A
3.3
3.3
3.3
Compressor 1 , Circuit 1
Motor Size
kW
4.6
5.6
6.3
Nominal Run Amps
A
8.5
11.4
13.3
Locked Rotor Amps
A
70
87
100
Type of Start
Direct On Line
Compressor 2, Circuit 1
Motor Size
kW
4.6
5.6
6.3
Nominal Run Amps
A
8.5
11.39
13.27
Locked Rotor Amps
A
70
87
100
Type of Start
Direct On Line
Standard Condenser Match - AC Motor Per Fan
Quantity x Motor Size
kW
2x 0.6
2 x 0.6
2 x 0.6
Full Load Amps
A
2.62
2.62
2.62
OPTIONAL EXTRAS
Electric Heating
Number of stage of Reheat
2
2
2
Number of Elements
6
6
6
Rating (Total)
kW
21
21
21
Current Per Phase
A
30.31
30.31
30.31
Humidifier
Capacity
kg/hr
8
8
8
Rating
kW
6
6
6
Full Load Amps
A
8.67
8.67
8.67
First upgrade Fan Motor - EC Motor - Per Fan
Quantity x Motor Size
kW
2 x 3.1
2 x 3.1
2 x 3.1
Full Load Amps
A
4.8
4.8
4.8
Locked Rotor Amps
A
4.8
4.8
4.8
Second upgrade Motor - EC Motor - Per Fan
Quantity x Motor Size
kW
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
N/A
Standard Condenser Match - EC Motor-Per Fan
Quantity x Motor Size
kW
2 x 0.73
2 x 0.73
2 x 0.73
Full Load Amps
A
3.3
3.3
3.3
Condenser Match - SCAF Fan
Quantity x Motor Size
kW
2 x 1.4
2 x 1.4
2 x 1.4
Full Load Amps
A
6
6
6
(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed
(3) Values are per compressor
X
2
C
0