Performance Data – Water Cooled Models
Cooling Duties
Cooling Capacity (1)
Condenser Entering / Leaving Temperature - Based on
∆
T of 5°C
Air On °C DB
25°C/30°C
30°C/35°C
35°C / 40°C
40°C/45°C
/%RH
TC
(kW)
SC
(kW)
THR
(kW)
TC
(kW)
SC
(kW)
THR
(kW)
TC
(kW)
SC
(kW)
THR
(kW)
TC
(kW)
SC
(kW)
THR
(kW)
SC19D055-W2W2-0
2 x DR40
22/50
52.4
48.8
67.2
52.4
48.8
67.2
51.9
48.6
67.1
49.2
47.4
66.4
24/45
53.5
52.4
68.3
53.5
52.4
68.3
53.0
52.2
68.2
50.2
50.2
67.4
26/40
54.5
54.5
69.3
54.5
54.5
69.3
54.0
54.0
69.2
51.2
51.2
68.4
SC19D070-W2W2-0
2 x DR55
22/50
65.2
59.8
83.9
65.2
59.8
83.9
65.2
59.8
83.9
63.1
58.8
83.3
24/45
66.9
64.2
85.6
66.9
64.2
85.6
66.9
64.2
85.6
64.7
63.4
84.9
26/40
68.3
68.3
87.0
68.3
68.3
87.0
68.3
68.3
87.0
66.1
66.1
86.3
SC19D080-W2W2-0
2 x DR55
22/50
74.2
67.2
95.8
74.2
67.2
95.8
74.2
67.2
95.8
71.5
66.0
94.9
24/45
76.1
72.2
97.7
76.1
72.2
97.7
76.1
72.2
97.7
73.3
71.0
96.7
26/40
77.7
77.5
99.3
77.7
77.5
99.3
77.7
77.5
99.3
74.8
74.8
98.3
SC25D080-W2W2-0
2 x DR55
22/50
75.7
69.8
97.3
75.7
69.8
97.3
75.7
69.8
97.3
72.9
68.4
96.3
24/45
77.6
75.1
99.2
77.6
75.1
99.2
77.6
75.1
99.2
74.7
73.6
98.1
26/40
79.3
79.3
100.8
79.3
79.3
100.8
79.3
79.3
100.8
76.3
76.3
99.7
SC25D090-W2W2-0
2 x DR70
22/50
82.4
76.5
106.9
82.4
76.5
106.9
82.4
76.5
106.9
79.7
75.2
106.0
24/45
84.6
82.3
109.1
84.6
82.3
109.1
84.6
82.3
109.1
81.7
80.9
108.1
26/40
86.4
86.4
110.9
86.4
86.4
110.9
86.4
86.4
110.9
83.5
83.5
109.9
SC25D100-W2W2-0
2 x DR70
22/50
93.9
85.6
122.1
93.9
85.6
122.1
93.9
85.6
122.1
90.6
83.8
121.3
24/45
96.3
91.7
124.5
96.3
91.7
124.5
96.3
91.7
124.5
92.9
90.0
123.6
26/40
98.3
98.3
126.6
98.3
98.3
126.6
98.3
98.3
126.6
94.8
94.8
125.6
SC31D100-W2W2-0
2 x DR70
22/50
95.8
86.2
124.1
95.8
86.2
124.1
95.8
86.2
124.1
92.1
84.4
122.8
24/45
98.3
92.5
126.6
98.3
92.5
126.6
98.3
92.5
126.6
94.5
90.7
125.3
26/40
100.3
99.3
128.7
100.3
99.3
128.7
100.3
99.3
128.7
96.5
96.5
127.3
SC31D120-W2W2-0
2 x DR95
22/50
109.6
99.1
141.7
109.6
99.1
141.7
109.6
99.1
141.7
105.0
96.9
140.2
24/45
112.4
106.4
144.6
112.4
106.4
144.6
112.4
106.4
144.6
107.7
104.3
143.0
26/40
114.8
114.4
147.0
114.8
114.4
147.0
114.8
114.4
147.0
109.9
109.9
145.3
SC31D130-W2W2-0
2 x DR95
22/50
117.2
105.7
151.6
117.2
105.7
151.6
117.2
105.7
151.6
112.2
103.4
150.2
24/45
120.2
113.4
154.7
120.2
113.4
154.7
120.2
113.4
154.7
115.0
111.1
153.1
26/40
122.8
122.1
157.4
122.8
122.1
157.4
122.8
122.1
157.4
117.5
117.5
155.7
TC=Total Cooling SC=Sensible Cooling THR=Total Heat of Rejection
(1) All data quoted is gross
(2) Deduct fan gain for net duties, refer to
Mechanical Data
(3)
Interpolate for water temperatures between those quoted, do not extrapolate
(4) Water flow rate (l/s)= THR/(4.19 x
∆
T) at 100% Water
W
2
W
2