Te
ch
nic
al
Chillers
TurboChill™ R1234ze Air Cooled and FreeCool
101
Chiller Technical Manual 7752785 V1.12.0_10_2018
Fre
eC
oo
l
TCF23X12G-24, TCF23X14G-24
Technical Data
Electrical Data
Electrical Data
Units
TCF23X12G-24
TCF23X14G-24
Unit Data
Full Load Amps (1)
A
497
505
Maximum Start Amps
A
347
355
Mains Supply
VAC
400V (±10%) 3PH 50Hz
Recommended Mains Fuse Size
A
560
560
Max Mains Incoming Cable Size (Direct
to 3 Phase Mains Isolator)
mm²
2x 300mm² (Torque >20Nm)
Independent Permanent Supply
Recommended Fuse Size
A
25
25
Independent Permanent Supply
VAC
230V 1PH 50Hz (±10%)
Max Permanent Incoming Cable Size
(Direct to Control Panel Isolator)
mm²
6mm² / 8 AWG
Control Circuit
VAC
24 VAC & 230VAC (±10%)
Evaporator
Immersion Heater Rating
W
340 (2x 170)
340 (2x 170)
External Trace Heating
Available (fitted by others)
W
500
500
Condenser Fan - Per Fan (EC)
Quantity
12
14
Full Load Amps
A
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
Motor Rating
kW
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
150
150
Quantity
2 / 1
2 / 1
Motor Rating
kW
92
92
Start Amps
A
2
2
Type Of Start
Electronic Soft Start
(1) Based at full load Conditions and EC Fans
Pump electrical data is available from Airedale upon request.