Notes:
TCF11R06G-07
TCF11R08G-07
SEPR
1,3,5
8.0
8.4
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
269029.1
263900.0
Rated Refrigerant Capacity P
A
1,3,5
kW
287.6
297.6
Rated Power Input D
A
kW
94.6
93.3
Rated EER
DC,A
3.04
3.19
Declared Refrigerant Capacity P
B
1,3,5
kW
268.3
277.6
Declared Power Input D
B
kW
61.1
59.8
Declared EER
DC,B
4.39
4.64
Declared Refrigerant Capacity P
C
1,3,5
kW
249.0
257.6
Declared Power Input D
C
kW
40.1
39.0
Declared EER
DC,C
6.21
6.61
Declared Refrigerant Capacity P
D
1,3,5
kW
229.6
237.6
Declared Power Input D
D
kW
16.0
15.9
Declared EER
DC,D
14.34
14.97
SSCEE
2,3,5
%
185.7
195.6
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2,4,5
kW
290.0
300.0
Declared Cooling Capacity 35°C Pdc 2,3,5
kW
287.6
297.6
Declared EER
d
35°C
3.04
3.19
Declared Cooling Capacity 30°C Pdc 2,3,5
kW
211.3
218.7
Declared EER
d
30°C
4.18
4.44
Declared Cooling Capacity 25°C Pdc 2,3,5
kW
135.0
139.7
Declared EER
d
25°C
5.27
5.58
Declared Cooling Capacity 20°C Pdc 2,3,5
kW
93.3
91.6
Declared EER
d
20°C
6.23
6.50
Sound Power Level
dB(A)
88
88
Air Volume
m³/h
123975
165301
Off mode P
OFF
kW
0.249
0.249
Thermostat-off mode P
TO
kW
2.353
2.365
Standby Mode P
SB
kW
0.340
0.350
Crankcase heater mode P
CK
kW
0.000
0.000
Technical Data - TCF R
Ecodesign
TCF11R06G-07, TCF11R08G-07
Introduction
Chillers
TurboChill™ R1234ze Air Cooled and FreeCool
179
Chiller Technical Manual 7752785 V1.12.0_10_2018
Te
ch
nic
al
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.