TCF11X06G-07
TCF11X08G-07
SEPR
1,3,5
7.6
7.9
SEPR Tier
Tier 2 (2021)
Tier 2 (2021)
Annual Electricity Consumption
kWh/a
242689.6
243217.0
Rated Refrigerant Capacity P
A
1,3,5
kW
248.3
258.3
Rated Power Input D
A
kW
88.0
85.8
Rated EER
DC,A
2.82
3.01
Declared Refrigerant Capacity P
B
1,3,5
kW
231.7
241.0
Declared Power Input D
B
kW
56.1
55.3
Declared EER
DC,B
4.13
4.36
Declared Refrigerant Capacity P
C
1,3,5
kW
215.0
223.7
Declared Power Input D
C
kW
36.5
35.8
Declared EER
DC,C
5.89
6.24
Declared Refrigerant Capacity P
D
1,3,5
kW
198.3
206.3
Declared Power Input D
D
kW
14.1
14.7
Declared EER
DC,D
14.04
13.99
SSCEE
2,3,5
%
169.6
175.9
SSCEE Tier
Tier 2 (2021)
Tier 2 (2021)
Rated Cooling Capacity P
rated,c
2,4,5
kW
250.0
260.0
Declared Cooling Capacity 35°C Pdc 2,3,5
kW
248.3
258.3
Declared EER
d
35°C
2.82
3.01
Declared Cooling Capacity 30°C Pdc 2,3,5
kW
182.6
189.9
Declared EER
d
30°C
3.87
4.07
Declared Cooling Capacity 25°C Pdc 2,3,5
kW
116.8
118.7
Declared EER
d
25°C
4.48
4.53
Declared Cooling Capacity 20°C Pdc 2,3,5
kW
93.2
91.5
Declared EER
d
20°C
5.96
6.28
Sound Power Level
dB(A)
87
87
Air Volume
m³/h
123975
165301
Off mode P
OFF
kW
0.249
0.249
Thermostat-off mode P
TO
kW
1.658
1.682
Standby Mode P
SB
kW
0.340
0.350
Crankcase heater mode P
CK
kW
0.000
0.000
Technical Data - TCF X
Ecodesign
TCF11X06G-07, TCF11X08G-07
Introduction
Chillers
TurboChill™ R1234ze Air Cooled and FreeCool
187
Chiller Technical Manual 7752785 V1.12.0_10_2018
Te
ch
nic
al
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.