Ultima Compact™
Chillers
41
Ultima Compact 30-150kW Technical Manual 9690553 V1.2.0_10_2019
Lifting Dimensions
E
A
B
C
D
Number of
Fans
Eye Bolt
Size
A
(mm)
B
(1)
(mm)
C
(mm)
D
(mm)
E
(mm)
UCCL 85-100
2
M24
290
1900
585
2500
1300
UCCL 125-150
3
M24
290
2015
1320
2500
1300
UCCL 125-150
4
M24
290
2870
1315
3000
1300
Installation
Positioning
Mains Isolation
To comply with BS EN 60204-1:2006 Safety of Machinery – Electrical Equipment Machines, each unit shall have an
accompanying isolator (switch disconnecting device). The isolator and emergency stop must be easily accessible
and, in compliance with the Safety of Machinery – Electrical Equipment Machines Standard (BS EN 60204-1), the
isolator handles and emergency stop shall be no higher than 1.9m above the service level. A maximum height of 1.7m
is recommended, whether directly from the service level or from a permanently fixed service level, to ensure ease of
accessibility.
If the unit is mounted on a raised plinth, the upper limit of 1.9m must be observed and a permanently fixed service
platform must be installed to maintain the 1.9m maximum height allowance. Suitable access to the isolator and
emergency stop must be provided and maintained from the point of power being applied to the unit prior to
commissioning. If service level access or permanently fixed access cannot be provided at this point, a suitable temporary
platform needs to be in position before the unit can be switched on or commissioned, and should remain in place until a
suitable permanent solution is available.
Service Level
1.9m Maximum
Ins