ULTIMA REMOTE AIR COOLED
Chillers
28
Chillers
Installation & Maintenance : 6259535 IM E 02/2013
Commissioning Data
OPERATING LIMITS
(For 100% Water)
Minimum Ambient Air DB °C
-5°C
Maximum Ambient Air DB °C
Refer to
Technical Manual
Minimum Leaving Water Temperature °C
+6°C
Maximum Return Water Temperature °C
+20°C
1
Temperatures lower than those stated can be obtained with the addition of glycol.
2
For conditions outside those quoted, please refer to Airedale.
MECHANICAL DATA
Oil & Refrigerant Charges
URAC75
URAC100
URAC125
URAC150
URAC175
Compressor
Tandem Scroll
– Hermetic
Quantity
4
4
4
4
4
Oil Charge Volume (Total)
l
4 x 4.1
4 x 4.1
4 x 4.1
4 x 4.1
2 x 4.7 + 4.1
Oil Type
Polyol Ester
Refrigeration
Dual Circuit
Refrigerant Control
Electronic Expansion Valve
Refrigerant Type
R407C
Holding Charge
Dry Nitrogen
URAC200
URAC225
URAC240
URAC250
URAC270
Compressor
Tandem Scroll - Hermetic
Trio Scroll
–
Hermetic
Tandem Scroll -
Hermetic
Trio Scroll
–
Hermetic
Quantity
4
4
6
4
6
Oil Charge Volume (Total)
l
4 x 4.7
2 x 6.3 + 4.7
6 x 4.1
4 x 6.3 3 x 4.7 & 3 x 4.1
Oil Type
Polyol Ester
Refrigeration
Dual Circuit
Refrigerant Control
Electronic Expansion Valve
Refrigerant Type
R407C
Holding Charge
Dry Nitrogen
URAC300
URAC330
URAC360
URAC400
URAC450
Compressor
Trio Scroll - Hermetic
Quantity
6
6
6
6
6
Oil Charge Volume (Total)
l
6 x 4.7
2 x 6.3 + 4.7
6 x 6.3 3 x 5.9 & 3 x 6.3
6 x 5.9
Oil Type
Polyol Ester
Refrigeration
Dual Circuit
Refrigerant Control
Electronic Expansion Valve
Refrigerant Type
R407C
Holding Charge
Dry Nitrogen