background image

21

© Airflow - We reserve the right to make changes without prior notice

DV51  DV51CH

Input power (total) (W)

Air flow (max) (l/sec)

SFP =

SFP rate (Specific Fan Power)

recommended value <1.8 (kW m

3

/s)

FAN INPUT POWER

SUPPLY/EXTRACT AIR VOLUMES

Pressure loss in ducts. Total pressure 

(Pa)

Volume flow rate 

(l/sec)

extract air

supply air

Volume flow rate

Power (W)

Sound values have been measured at the measurement points of the facility curve (L) of the air flow graph. The values 

change very little when the pressure loss in the ducts is low and the fan settings remain unchanged . The sound values 

increase when the pressure loss in the ducts increase .

TECHNICAL

 SPECIFICA

TIONS

AIR FLOWS AND SOUND VALUES

Sound values

Sound power level in the supply air duct (one duct) by octave band 

L

w

, dB

Sound power level in the extract air duct (one duct) by octave band 

L

w

, dB

Adjustment position

Adjustment position

Adjustment 

position (%)

10

20

30

40

50

60

70

80

90

100

10

20

30

40

50

60

70

80

90

100

Medium 

fre-

quency 

of the 

octave 

band 

Hz

63

58

60

62

64

66

68

73

81

81

81

52

52

55

55

59

61

72

70

72

72

125

47

52

57

59

62

65

67

68

68

68

52

52

54

55

56

58

60

62

62

62

250

44

50

55

57

64

62

65

67

67

67

30

33

39

42

44

47

50

51

52

51

500

39

46

52

54

57

59

62

65

66

67

30

38

40

42

46

49

50

54

56

55

1000

32

40

45

48

52

56

59

64

64

64

20

27

31

34

37

39

42

45

46

46

2000

21

30

37

42

45

48

51

53

53

53

13

15

20

24

28

30

33

35

36

36

4000

18

22

30

36

42

46

49

52

52

52

17

17

17

18

18

19

21

23

23

23

8000

21

21

23

27

34

40

44

48

48

48

21

21

21

21

21

21

21

21

21

21

L

W

, dB

58

61

64

66

70

71

75

82

82

82

55

55

58

58

61

63

72

71

73

73

L

WA

, dB(A)

41

47

52

55

59

61

64

67

68

68

37

39

42

44

46

49

51

54

55

55

Adroit 51 MV, Adroit DV51CH (no standard extraction through the hood in the kitchen) 

Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)

Adjustment position

Adjustment 

position (%)

10

20

30

40

50

60

70

80

90

100

L

pA

, dB (A)

21

24

28

29

32

35

38

40

40

40

Adroit DV51CH (standard extraction 8 dm³/s through the hood in the kitchen)

Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)

Adjustment position

Adjustment 

position (%)

22

40

L

pA

, dB (A)

28

32

0

10

20

30

40

50

60

70

0

36

72

108

144

180

216

252

m³/h

30 %

50 %

10 %

20 %

40 %

60 %

70 %

80 %

(l/s)

100 %

0

10

20

30

40

50

60

70

80

dm³/s

25 %

5 %

15 %

45 %

0

50

100

150

200

250

300

350

0

10

20

30

40

50

60

70

80

55 %

65 %

35 %

100 %

SFP 1,8  

SFP 1,5 

SFP 1,2 

SFP 1,0  

SFP 0,8  

L

0

36

72

108

144

180

216

252

m³/h

(l/s)

dm³/s

288

SOUND VALUES

TECHNICAL

 SPECIFICA

TIONS

Summary of Contents for Adroit DV51

Page 1: ...Instruction Manual INSTRUCTION MANUAL DV51 DV51CH...

Page 2: ...on 13 Adjustment 13 Adroit DV51 DV51CH 15 Dimensions and duct outlets 15 MAINTENANCE 16 Adroit DV51 DV51CH 16 Before beginning maintenance work 16 Changing the filters 16 Cleaning the heat recovery ce...

Page 3: ...the right In the left handed version outdoor air blows into the unit from the left side The location of the filters bypass damper and brine heat exchanger not supplied as standard is also mirrored in...

Page 4: ...Service section 4 Registration Page is now opened 5 Enter the following information a Device name enter the desired name for the device b User name c E mail address d Password 6 Press the create acco...

Page 5: ...work and structures causing moisture damage You can control and automate the ventilation unit operation in the following ways By using an Adroit control panel installed in the building Through the Adr...

Page 6: ...ntilation A sufficient supply air flow must be ensured in the room if the cooker hood is to be used simultaneously with non electronic devices Adroit DV51CH The Adroit DV51CH ventilation unit is contr...

Page 7: ...3 Adjust the brightness of the light by pressing the light button until the brightness is adequate 4 To save the setting press the selection button for roughly 3 seconds until the setting mode light...

Page 8: ...L model the parts are mirrored MAIN PARTS Adroit DV51 Post heating resistor 8 Control panel 9 Internal humidity sensor 10 Internal carbon dioxide sensor 10 Humidity sensor optional 11 Carbon dioxide s...

Page 9: ...al 9 R model in the figure In the L model the parts are mirrored MAIN PARTS Adroit DV51CH Internal humidity sensor 10 Internal carbon dioxide sensor 10 Humidity sensor optional 11 Carbon dioxide senso...

Page 10: ...ctric connections The length of the wires must enable pulling the fan chamber assembly out of the unit without having to disconnect any of the connections NOTE A space of at least 330 mm must be reser...

Page 11: ...m of the Adroit DV51CH ventilation unit marking the position where the condensing water tube must be installed 1 Install the elbow at the bottom of the ventilation unit without the siphon Figure 1 Ins...

Page 12: ...lation unit Push in place Figure 2 3 Ensure that the feedthrough seal of the condensing water tube sits firmly around the tube 4 Lift the front of the cooker hood to fit the mountings into the penetra...

Page 13: ...d ventilation The volume flow rate of the air inside the cooker hood is measured with the damper closed and where required adjusted based on the static pressure loss and the performance scheme of the...

Page 14: ...ooker hood extract air D Supply air fan E Extract air fan R model in the figures In the L model the order of the ducts is mirrored C B A B A D E D E Adroit DV51CH Adroit DV51 INSTALLATION Damper in th...

Page 15: ...lowing outdoors from the unit 3 Supply air from the unit to the apartment 4 Extract air from the apartment to the unit L model R model INSTALLATION 239 103 81 598 96 155 141 141 143 1 2 3 4 239 103 81...

Page 16: ...ilter replacement interval depends on the ambient particle concentration It is recommended that the filters be replaced every spring and autumn or at the very least once a year To replace the filters...

Page 17: ...dirty clean it by immersing it in warm water to which a small amount of a mild detergent has been added 6 Rinse the cell clean with a water spray Do not use a high pressure cleaner 7 When all the wate...

Page 18: ...ve the bar from the joint of the damper Turn the crank of the damper motor so that the bar comes off from the bypass damper and turn the damper into the cell bypass position 8 Pull out the upper suppo...

Page 19: ...the grease filter 1 Pull the locking device of the grease filter towards the front edge of the cooker hood while pulling the grease filter downwards until it comes off 2 Clean the grease filter eithe...

Page 20: ...FP 70 A 84 0 94 kW 25 l sect Dimensions w x h x d 598x668x349 mm Weight 60 kg TECHNICAL SPECIFICATIONS ADROIT DV51CH Product title Adroit DV51CH R Adroit DV51CH L Adroit white hood Adroit stainless st...

Page 21: ...7 30 33 39 42 44 47 50 51 52 51 500 39 46 52 54 57 59 62 65 66 67 30 38 40 42 46 49 50 54 56 55 1000 32 40 45 48 52 56 59 64 64 64 20 27 31 34 37 39 42 45 46 46 2000 21 30 37 42 45 48 51 53 53 53 13 1...

Page 22: ...CAL CONNECTION Adroit 51 Adroit DV51CH 1 4 5 2 3 6 1 2 3 4 5 90 C 130 C T2 T1 230V 50Hz GN C B YE WT BN YEGN BU BN BU BN BU BU BU BN BN 2 3 1 R1 YE GN YEGN BN BU WH A Motherboard B 1 Extract air fan t...

Page 23: ...TION OPEN ACTIVATED CLOSED HOUSE AUTOMATION NORMAL SITUATION OPEN ERROR SITUATION HOOD OR VENTILATION UNIT CLOSED ACTIVATED GUARD FUNCTION FLASHING POSITION OF THE DAMPER DAMPER CLOSED CONTACT OPEN DA...

Page 24: ...l mp tila anturin liitin D I1 Digitaalinen tulo 1 D I2 Digitaalinen tulo 2 Ethernet liit nt ja pistotulppa koneen p ll MOTHERBOARD UNDER COVER VALLOX 51 MV VALLOPLUS 180MV Potentiaalivapaa k rkitieto...

Page 25: ...5 0 5 2x2x0 5 0 5 3 x 1 5 MyVallox Control 2x2x0 5 0 5 2x0 5 2x0 5 2x2x0 5 CAT Kytkent rasian max tehonsy tt 6W 2x0 5 MyVallox RH transmitter MyVallox VOC transmitter Adroit RH sensor Adroit Control...

Page 26: ...ignal RS_B Local hardware Modbus B signal 11V1 11 1 V operating voltage AN I Analog input 0 10VDC RM I 24V relay input RM O 24V relay output P Circulation pump V Solenoid valve Ethernet connection on...

Page 27: ...pecified in the temperature setting In winter the Brine heat exchanger will turn on when the outdoor temperature falls below the winter setting Manual In summer the Brine heat exchanger will turn on w...

Page 28: ...luded in the delivery The valve that is chosen must be compatible with the heat collection circuit fluid for example ELV05006 Stig Wahlstr m K Condensing water tube Not included in the delivery IP De...

Page 29: ...00571 5 HR cell 60000566 14 RJ 45 extension cable 60000209 23 Lock nut of the door screw supplied together with the door screw 60000561 6 Lower support for HR cell 60000565 15 Internal humidity and CO...

Page 30: ...LED power source 60000574 6 Lower support for HR cell 60000565 18 Adroit humidity sensor optional 90000612 30 Motherboard 60000575 7 Fan chamber assembly R 60000583 19 Adroit CO2 sensor optional 9000...

Page 31: ...droit Declare that the ventilation unit for supply and extract air equipped with heat recovery and operating as part of a ventilation system has been designed and manufactured to the following specifi...

Page 32: ...it Has been installed and used in accordance with the fitting and wiring instructions supplied with each unit Has not been connected to an unsuitable electrical supply Has not been subjected to misuse...

Reviews: