background image

þ
þ
þ

energy

bulbs

.co.uk

Mon-Fri:

 8:30am - 6:30pm  

|  Sat & Sun:

 11am - 5pm

08

00 0

43 8

97

8

or 0121 250 2180

Quick 

O

rder Hotline

G

uaranteed Low Prices

Huge Stock Available

Airflow Stockist

4.0 Electrical connection 

All work must be carried out with the equipment fully isolated from the power supply. The electrical connection
is to be carried out in accordance with the relevant wiring diagram and are only to be done by a certified
electrician. The fans may not be operated with transformer controllers.

All relevant safety regulation, national standards and norms are to be adhered to. 

4.1 Electronic control board

The electronic control board allows the operation with 2 speeds (75/90 m

3

hr) for QT100T and (150/170 m

3

hr) for

QT120T. The control board is fitted into a splash-proof casing.

EMV regulation
Important indication for the electromagnetic compatibility

Interference resistance according to DIN EN 55014-2 depending upon impulse form and energy rate of 1000 V to 
4000 V. With operation with fluorescent tubes, switch power supplies, electronically regulated halogen bulbs etc. these
values can be exceeded.
In  this case additional suppression shielding activities are necessary (L -, C or RC elements, protection diodes, 
resistors).

5.0 Cleaning and maintenance

- Before cleaning, ensure that the fan is isolated from the power supply.
- Prevent unintentional restart !
- Clean device only with a damp cloth.
- The device is maintenance-free.

5.1 Dismantling of fascia

Procedure:

1. Isolate the device from the power supply and prevent unintentional restart!
2. Remove the fascia (1) by using the correct tool (e.g. screw driver) and applying light pressure on the spring catches

left and right of the fascia (Fig.10). 

3. Unfasten the screws of the control board cover (2) (Fig.11). 

6.0 Troubleshooting

- If the thermal protection trips this could be the result of dirt  build-up, a hard running impeller and/or bearings. 

Too high winding temperature through insufficient motor cooling, or too high air flow temperature could be the cause 
of disturbance.

- Abnormal noises can mean worn out bearings.
- Vibrations can originate from an unbalanced or dirty impeller or due to the installation.
- Extreme performance reduction can occur if the fan must work against too high resistance of the ventilation system

or if there is a lack of sufficient supply air (causing also higher sound level).

5

Installation and Operation Instructions

4

Installation and Operation Instructions

WARNING  

NOTE  

CHAPTER 4

ELECTRICAL
CONNECTION

CHAPTER 5

CLEANING AND
MAINTENANCE

CHAPTER 6

TROUBLESHOOTING

5

Wiring diagram overview
QT100T - 75(90)m

3

/hr

QT120T - 150(170)m

3

/hr

Electrical connection:

- Terminal N / L:

The supply voltage of 230 V is connected permanently to
terminal N/L

- Terminal 1:

The time functions are activated via terminal 1.

The following functions are implemented:

1. Start delay (0 sec, 45 sec, 90 sec, 120 sec)
DIP-switch S1-2

(see wiring diagram SS-920.2)

After switching on terminal 1, the fan starts first after the adjusted
delayed time. Thus a room can be entered for a short time (via
two-pole switch) e.g. during combined on/off switching with the
light without the fan being started for operation. Factory setting
approx. 120 sec.

2. Operation with push-button switch

During start delay the fan can be switched on via terminal 1 with a
push-button switch at deactivated start delay (sampling pulse min.
0,5 sec.).

3. Run on time (6 min., 10 min., 15 min., 21 min.)
DIP-switch S3+4

(see wiring diagram SS-920.2)

After switching off terminal 1, the fan keeps running and switches
off after the adjusted time automatically. Factory setting approx.
15 min.

4. Interval operation (0 hrs., 8 hrs., 12 hrs., 24 hrs.)
DIP-switch S5+6

(see wiring diagram SS-920.2)

The fan can be put in adjustable time intervals into operation auto-
matically. After the adjusted run on time the fan switches off auto-
matically. The interval time starts after the last switch off process
on terminal 1 (time input), also with manual operation in the mean-
time (terminal 2). The manual operation does not have influence on
the interval operation. The turn-on time in the interval operation
corresponds to the adjusted run on time. Factory setting approx. 0
hrs.
In delivered condition the interval operation is deactivated. The DIP
switches have to be adjusted according to the table for a desired
interval.

5. Changing the factory setting

DIP-switch (see wiring diagram SS-920.2). Isolate the unit from the
mains electric supply !

- Terminal 2:

The continuous operation is activated via terminal 2 (see wiring
diagram SS-917). With activated time function, the manual stage
(terminal 2) is inactive.

Room lighting

In connection with the room lighting (terminal 1 or 2), a two-pole
switch must be used.

SS-931

M1/... N

SS-917

1

2

a) Zeitfunktion
b) manuell Ein

1 2

L

N

N

L

b)

a)

M1/... NC

Important: Wiring in parallel

Wiring in parallel of several fans is not permitted.

- Jumper

Depending on the jumper setting, the fan QT100T runs with 75 or 90 m³/h or rather the fan
QT120T with 150 or 170 m³/h.

Jumper 1 (see wiring diagram SS-931)
QT100T / QT 120T

Position A – Factory setting
Kl. 1 = 75 m³/h / 150 m³/h, activation via time function
Kl.2 = 90 m³/h / 170 m³/h, manual on

Position B
Kl.1 = 90 m³/h / 170 m³/h, activation via time function
Kl.2 = 75 m³/h / 150 m³/h, manual on

Operation test – Test mode:

When applying the supply voltage the fan is in the test mode for 1 minute.
(Requirement: Factory setting of DIP-switch, see wiring diagram SS-920.2)
In this case the delayed start and the overrun function is deactivated within the first
minute, or for a switching cycle.

Internal functional principle / Jumper position

Connection client

WARNING

S

SS-920.2

Adjustment of DIP-switchs

a) time function
b) manual on

M1~

L

N

1

2

Kl.1=

Jumper 1

A / B

A

B

Zeit-Eingang

Manueller-Eingang

1 2

L

N

Kl.2=

Kl.1=
Kl.2=

time function/- input

manual input

S1

1 2

L

N

QT ... T

Einschaltv erzöger ung

Dela yed star t

Démarrage tempor isé

Nachlauf /

Einschaltz eit

Intervallzeit,

Einschaltdauer =

Nachlauf ze it

1

2

3

4

55

off

on

off

off

on

off

off

on

on

on

off

off

on

off

off

on

on

on

0 sec

45 sec

6 min

10 min

15 min

21 min

0 Std

8 Std

12 Std
24 Std

DIP-Schalter

/

Switch / Commutateur

Run on time  /

Running time

Temporisation /

Durée de f onctionnement

Interval time

Running time = Run on time
Durée inter valle

Durée de f onctionnement  =

Temporisation

off

on

1 2 3 4 5 6

6

off

on

90 sec

120 sec

off

off

on

on

9041551_Model_QT_100_120T  30/06/2010  11:29  Page 3

energybulbs

.co.uk

energybulbs

.co.uk

Summary of Contents for QT 100T

Page 1: ...ailable Airflow Stockist Installation and Operating Instructions QuietAir 100 120mm Axial Fan MODEL QT 100T Two Speed Fan 75 90m3 hr QT 120T Two Speed Fan 150 170m3 hr with Delay Start and Adjustable Timer control Low Energy Whisper Quiet Long Life Extra Safe Delay Start Auto Refresh Intervals ate of 9041551 Issue 1 01 13 n e r g y b u l b s c o u k ...

Page 2: ...on Page 2 1 11 Overview of types QT100T QT120T Page 2 1 12 Accessories Page 2 CHAPTER 2 SCOPE OF DELIVERY AND ASSEMBLY Page 2 2 0 Scope of delivery packing unit Page 2 CHAPTER 3 INSTALLATION Page 2 3 0 Preparation for wall or ceiling installation surface mounted Page 2 3 1 Cable exit from the wall Page 2 3 2 Drill holes Page 2 3 3 Wall or ceiling installation Page 3 3 4 Cable connection Page 3 CHA...

Page 3: ...pecially over longer distances check if the packing is adequate for method and manner of transportation Damages due to improper transportation storage or putting into operation are not liable for warranty 1 6 Application Operation The fans are designed for air extraction of living spaces If the unit is to be used in other applications where high humidity excessive dust temperature in excess of 40 ...

Page 4: ... been damaged in transit 3 0 Preparation for wall or ceiling installation surface mounted The assembly and start up of the fan unit should be carried out first after finishing all other work and after the final cleaning in order to avoid damage and contamination of the fan unit The position of the cable exit is variable see fig 2 3 3 1 Cable exit from the wall Distance to the duct centre depending...

Page 5: ...le through grommet don t cut open 2 Cut cable at least to length 180 mm and remove cable jacket at least 100 mm in length 3 Connect fan according to wiring diagram see page 5 4 Run cable in the conduit Ensure cable grommett is sealed to maintain IP45 1 Press cover of control board 2 on casing and fasten with screws 2 Snap in fascia 1 Length of single conductor 100 mm Length of stripped insulation ...

Page 6: ...power supply Prevent unintentional restart Clean device only with a damp cloth The device is maintenance free 5 1 Dismantling of fascia Procedure 1 Isolate the device from the power supply and prevent unintentional restart 2 Remove the fascia 1 by using the correct tool e g screw driver and applying light pressure on the spring catches left and right of the fascia Fig 10 3 Unfasten the screws of t...

Page 7: ... condition the interval operation is deactivated The DIP switches have to be adjusted according to the table for a desired interval 5 Changing the factory setting DIP switch see wiring diagram SS 920 2 Isolate the unit from the mains electric supply Terminal 2 The continuous operation is activated via terminal 2 see wiring diagram SS 917 With activated time function the manual stage terminal 2 is ...

Reviews: