background image

INSTALLATION INSTRUCTIONS

CAUTION:

 

MAKE SURE POWER IS SWITCHED OFF AT 

SERVICE PANEL BEFORE STARTING INSTALLATION.

SECTION 1

Preparing the Exhaust Fan

1. 

Unpack fan from the carton and confirm that all pieces are present. In addition to the 

exhaust fan you should have:

 

 

1 - Grill 

1 - Hardware Bag

 

 

1 - Damper Assembly (attached) 

 

1 - Electrical Connector

 

 

1 - Mounting Bracket 

  3 - Wire Nuts

 

 

1 - Instruction/Safety Sheet   

2. 

Remove the wire compartment cover and store in the carton until needed so it does not 

get damaged or lost 

(Figure 1).

3. 

Choose the location for your fan. To ensure the best 

air and sound performance, it is recommended that 

the length of ducting and the number of elbows be 

kept to a minimum, the radius of each elbow be as 

large as possible for the installation, and that insulated 

hard ducting be used. Larger duct sizes will reduce 

noise and airflow restrictions.

4. 

Select the most convenient electrical 

knockout and remove using a straight- 

blade screw driver 

(Figure 2).

5. 

No additional vibration deadening materials are 

needed for this fan.

SECTION 2

New Construction - BFQ Models

1. 

Using the gauge on the mounting bracket, line up the bracket on the joist so the bottom 

of the fan will be flush with the finished ceiling. Nail or screw the bracket in place 

securely 

(Figure 3).

WARNING:

 PROPER INSTALLATION REQUIRES A MINIMUM OF 4 

SCREWS LOCATED IN HOLES CLOSEST TO DRYWALL.

2. 

Snap the fan body into the 

bracket 

(Figure 4).

 The fan can 

be snapped into position with the 

duct collar facing to the left or the 

right depending which is most 

convenient. 

www.airkinglimited.com

210572021 Rev. U 11-18

2 of 8

New Construction - BFQW Models (Oval Duct)

1. 

Using the gauge on the bracket, line up the bracket on the side of a wall stud such that 

the bottom of the fan will be flush with the finished wall. The bracket should sit one 

drywall thickness forward on the stud 

(Figure 5).

NOTE:

 For proper damper operation, the duct 

adaptor must be facing up towards the ceiling.

NOTE:

 ½” minimum thickness drywall must be used for 

wall mount applications.
2. 

Nail or screw the bracket in place securely.

3. 

Snap the fan body into the bracket, making 

sure the duct collar is pointing upwards 
towards the ceiling 

(Figure 6).

 

SECTION 3

Existing Construction - BFQ Models

1. 

Position housing against the joist 

or stud and trace an outline of 

the housing onto the ceiling/wall 

material. Set housing aside and cut 

opening, being careful not to cut 

or damage any electrical or other 

hidden utilities 

(Figure 7).

2. 

Line up the bracket on the joist so 

the bottom of the fan will be flush 

with the finished ceiling. Nail or 

screw the snap-in bracket in place 

securely 

(Figure 3).

3. 

Snap the fan body into the bracket 

(Figure 4).

 The fan can be snapped into position 

with the duct collar facing to the left or the right depending which is most convenient.

Existing Construction - BFQW Models (Oval Duct)

1. 

Remove a section of the wall material large enough for you to fit the fan housing into as 

well as gain access to the top plate, and have enough space to connect the ducting. This 

will typically be across two studs and approximately 24" starting at the top of the wall.

2. 

Follow the instructions in 

Section 2

 - 

New Constructions - BFQW Models (Oval Duct)

 to 

complete the installation.

NOTE:

 Wall installation into existing construction will require you to patch the wall material 

around the unit.

SECTION 4

Ducting

NOTE: 4" OR LARGER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE.

CAUTION:

 ALL DUCTING MUST COMPLY WITH LOCAL AND NATIONAL 

BUILDING CODES.

1. 

Connect the ducting to the fan’s duct 

collar 

(Figure 8).

 Secure in place 

using tape or screw clamp. Always 

duct the fan to the outside through a 

wall or roof cap. It is recommended 

that low restriction termination 

fittings be used.

NOTE:

 For oval duct connection, squeeze 

standard 4" round rigid ducting to form 

an oval shape then follow instructions in 

Step 1

.

Figure 2

Figure 4

Figure 1

Figure 6

Figure 3

Figure 5

Drywall

Wall Stud

Figure 7

Round duct 

collar shown

Figure 8

Summary of Contents for BFQ Series

Page 1: ...stion and exhausting of gases through the flue chimney of fuel burning equipment to prevent back drafting Follow the heating equipment manufacturer s guideline and safety standards such as those published by the National Fire Protection Association NFPA and the American Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE and the local code authorities c When cutting or drilling...

Page 2: ...amper operation the duct adaptor must be facing up towards the ceiling NOTE minimum thickness drywall must be used for wall mount applications 2 Nail or screw the bracket in place securely 3 Snap the fan body into the bracket making sure the duct collar is pointing upwards towards the ceiling Figure 6 SECTION 3 Existing Construction BFQ Models 1 Position housing against the joist or stud and trace...

Page 3: ...ord into the receptacle This cord will only fit one way into the receptacle Figure 11 NOTE If using this fan to meet ASHRAE 62 2 requirements locate the label inside the fan housing and fill in the appropriate information 3 Install the grill by squeezing the two ends of the springs together and installing them up into the slots of the fan s housing Push the grill up into position Figure 12 4 Resto...

Page 4: ...G S LIABILITY UNDER ANY EXPRESS OR IMPLIED WARRANTY EXCEED THE PURCHASE PRICE OF THE PRODUCT AND ANY SUCH LIABILITY SHALL TERMINATE UPON THE EXPIRATION OF THE WARRANTY PERIOD Some states and provinces do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages so these exclusions or limitations may not apply to you This warra...

Reviews: