background image

www.airkinglimited.com

6728076 Rev. Q 3/22

2 of 12

INSTALLATION INSTRUCTIONS

CAUTION:

 

MAKE SURE POWER IS SWITCHED 

OFF AT SERVICE PANEL BEFORE STARTING INSTALLATION.

SECTION 1

Preparing the Fan

1. 

Unpack fan from the carton and confirm that all pieces are present. In addition to the fan 

you should have:

 

2 - Collar Assembly (attached) 

2 - Mounting Brackets (attached)

 

1 - Controller (attached) (QFAM Only)  1 - Instruction/Safety Sheet

2.  Choose the location for your fan. To ensure the best air and sound performance, it is 

recommended that the length of ducting and the number of elbows be kept to a minimum, 

the radius of each elbow be as large as possible for the installation, and that insulated hard 

ducting be used. This fan will require at least 12” of clearance in the ceiling or wall. The fan 

mounts using the provided mounting brackets or can be surface mounted to a wall or ceiling.

NOTE:

 

The fan must be installed into a location that can be easily accessed once installed.

3. 

No additional vibration deadening materials are needed for this fan.

SECTION 2

Mounting the Fan

1. 

Confirm the fan is positioned so the air flow is in the correct direction.

2a. 

Surface Mounting: 

Locate at least one stud or joist. Place the fan in position so that the 

mounting bracket is centered on the stud or joist and make the location for the four (4) 

holes. Remove the fan and install properly rated wall/ceiling anchors for the holes that do 

not go directly into a joist or stud. Position fan in place and secure with screws (not 

included) 

(Figure 1).

2b. 

Mounting to a Joist:

 Install two - 2 x 4 headers (not included) between the joists. Position 

the fan housing on top of the headers and secure the mounting brackets with screws (not 

included) to the header 

(Figure 2)

.

2c. 

Hanging Bar Mounting: 

Lift unit up onto the threaded rods and secure in place using 

appropriate hardware (not included) 

(Figure 3).

Figure 1

Screws

Stud/Joist

Anchor

Air Flo

w

Figure 2

Joist

2 x 4 Header

Bracket

12"

Figure 3

Bracket

Housing

Threaded Rod

SECTION 3

Ducting

NOTE: 6” OR LARGER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE.

CAUTION:

 

ALL DUCTING MUST COMPLY WITH LOCAL AND NATIONAL 

BUILDING CODES.

NOTE:

 The ducting from this fan to the outside of the building has a strong effect on the air 

flow, noise and energy use of the fan. Use the shortest, straightest duct routing possible for 

best performance, and avoid installing the fan with smaller ducts than recommended. Insulation 

around the ducts can reduce energy loss and inhibit mold growth. Fans installed with existing 

ducts may not achieve their rated air flow.

WARNING:

 

MAKE SURE THE FRESH AIR INTAKE PORT COMPLIES WITH 

ALL LOCAL AND NATIONAL CODES AND IS LOCATED AT LEAST 6 FEET AWAY 

FROM SOURCES OF CONTAMINATION SUCH AS BUT NOT LIMITED TO: DRYER, 

FURNACE OR CENTRAL VACUUM EXHAUSTS, GAS APPLIANCES SUCH AS BBQ GRILLS, 

GARBAGE BINS OR OTHER EXHAUST PORTS.
NOTE: 

To ensure quiet operation of in-line and remote fans, each fan shall be installed using sound 

attenuation techniques appropriate for the installation. This can typically be achieved by installing 

insulated flexible ducting between the exhaust or supply grille(s) and the fan. 
1. 

Connect the ducting to the fan’s duct collar 

(Figure 4).

 Seal ducting to housing with 

appropriately rated tape. Use screws or suitable clamps to secure in place. Make sure the 

fresh air intake is connected to a properly installed intake port that is a suitable weather 

hood with insect screen to protect air intake. It is recommended that low restriction 

termination fittings be used.

2. 

Ensure duct joints and exterior penetrations are sealed with caulk or other similar material 

to create an air-tight path to minimize building heat loss or gain and to reduce the potential 

for condensation. Place/wrap insulation around duct and/or fan in order to minimize possible 

condensation buildup within the duct, as well as building heat loss or gain.

NOTE:

 At the base of the duct adapter, there is a small diameter test port hole covered with a 

plastic cap. Make sure the test port is not covered up with the ducting so that it can be accessed 

for pitot tube testing. To access the port, remove the port cover and insert tube.

SECTION 4

Wiring

CAUTION:

 MAKE SURE POWER IS SWITCHED OFF AT SERVICE 

PANEL BEFORE STARTING INSTALLATION.

CAUTION:

 ALL ELECTRICAL CONNECTIONS MUST BE MADE 

IN ACCORDANCE WITH LOCAL CODES, ORDINANCES, OR NATIONAL 

ELECTRICAL CODE. IF YOU ARE UNFAMILIAR WITH METHODS OF 

INSTALLING ELECTRICAL WIRING, SECURE THE SERVICES OF A 

QUALIFIED ELECTRICIAN.

NOTE:

 This unit includes a side access panel for wiring that does not require the removal of the 

fan’s blower assembly.
1.  Remove the wire compartment cover screw and place cover in a secure place 

(Figure 5).

Figure 4

Air Flow

Intake  Ducting

Outlet  Ducting

Test Port

Figure 5

Screw

Wire 

Compartment 

Cover

Ground 

Screw

Summary of Contents for FAS

Page 1: ...Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment to prevent back drafting Follow the heating equipment manufacturer s guideline and safety standards such as those published by the National Fire Protection Association NFPA and the American Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE and the local co...

Page 2: ...t routing possible for best performance and avoid installing the fan with smaller ducts than recommended Insulation around the ducts can reduce energy loss and inhibit mold growth Fans installed with existing ducts may not achieve their rated air flow WARNING MAKE SURE THE FRESH AIR INTAKE PORT COMPLIES WITH ALL LOCAL AND NATIONAL CODES AND IS LOCATED AT LEAST 6 FEET AWAY FROM SOURCES OF CONTAMINA...

Page 3: ...present and for the temperature requirements of the installation to prevent air leakage from unconditioned spaces Additional material backing rod ceiling material are also not required NOTE This unit is equipped with a wire mesh insect screen Confirm that the screen is installed on the inside of the unit on the inlet ducting side 1 If the screen is not in place insert the screen into the tab at th...

Page 4: ...display press and hold the SetH button for 5 seconds to switch the display position of temperature and humidity When the temperature is higher than 150 F 65 C the display will show HI F When the temperature is lower than 15 F 10 C the display will show Lo F when the humidity is lower than 10 the display will show Lo When the detection temperature sensor and humidity sensor are abnormal is displaye...

Page 5: ...use unauthorized repairs made or attempted This warranty does not cover shipping costs for the return of products to Air King for repair or replacement Air King will pay return shipping charges from Air King following warranty repairs or replacement ANY AND ALL WARRANTIES EXPRESSED OR IMPLIED INCLUDING WITHOUT LIMITATION ANY IMPLIED WARRANTY OF MERCHANTABILITY LAST ONE YEAR FROM THE DATE OF ORIGIN...

Page 6: ...0001 2 1 6 Metal Collar Intake 5S1650002 3 1 6 Metal Collar Outlet 5S1650003 4 1 Blower Assembly 5S2202013 5 1 Wire Compartment Assembly 5S1650100 6 2 Adjustment Knobs 5S1299802 7 1 LCD Controller QFAM 5S1650043 8 1 Insect Screen 5S1650005 9 1 Access Panel 5S1650044 REPLACEMENT PARTS DIAGRAM 3 1 1 4 2 5 6 7 8 9 ...

Page 7: ...t b Avant d effectuer un service ou de nettoyer l unité couper l alimentation électrique dans le panneau de distribution et verrouiller le dispositif de déconnexionafind éviterquel alimentationnerevienneaccidentellement Lorsque le dispositif ne peut être verrouillé fixer solidement un avis d avertissement tel qu une étiquette au panneau de distribution AVERTISSEMENT POUR RÉDUIRE LES RISQUES D INCE...

Page 8: ...ance et évitez d installer le ventilateur avec des conduits plus petits que recommandé L isolation autour des conduits peut réduire la perte d énergie et empêcher le développement de moisissures Il se peut que les ventilateurs installés avec des conduits existants n atteignent pas leur débit d air nominal AVERTISSEMENT ASSUREZ VOUS QUE LE PORT D ADMISSION D AIR FRAIS EST CONFORME À TOUS LES CODES ...

Page 9: ...exigences de température de l installation Des matériaux supplémentaires tige de support matériau de plafond ne sont pas non plus nécessaires REMARQUE Cette unité est équipée d un grillage pour moustiquaire Assurez vous que le grillage est installé à l intérieur de l unité du côté des conduits d entrée 1 Si le grillage n est pas en place insérez le grillage dans la languette située à la base de l ...

Page 10: ... la température est supérieure à 65 C 150 F l écran affichera HI F Lorsque la température est inférieure à 10 C 15 F l écran affichera Lo F lorsque l humidité est inférieure à 10 l écran affichera Lo Lorsque le capteur de détection de température et le capteur d humidité est anormal s affichera Pour rétablir les réglages par défaut s assurer que l unité est au réglage OFF Appuyer sur le bouton éco...

Page 11: ...ou arrête de fonctionner en raison d un accident d une mauvaise manipulation ou opération de dommages d expédition d abus de mauvaise utilisation de réparation faite ou tentées non autorisées Cette garantie ne couvre pas les coûts d expédition pour le retour des produits à Air King pour la réparation ou le remplacement Air King payera les frais d expédition de retour de Air King après les réparati...

Page 12: ... 6 po d admission 5S1650002 3 1 Assemblée de collier en métal de 6 po sortie 5S1650003 4 1 Assemblée de la Soufflante 5S2202013 5 1 Assemblée du compartiment du fil 5S1650100 6 2 Boutons de réglage 5S1299802 7 1 Contrôleur LCD QFAM 5S1650043 8 1 Écran pour les insectes 5S1650005 9 1 Panneau d accès 5S1650044 SCHÉMA DES PIÈCES DE RECHANGE 3 1 1 4 2 5 6 7 8 9 ...

Reviews: