4. Operation
4
-
6
Install a switch between the output terminal and the
load to switch on/off the load. Do not switch the load
on/off directly by the circuit-breaker of the generator.
It could cause damage to the circuit-breaker.
Connect the connecting cable to the load so that the
output terminals should not touch each other.
4.3.1 Proper Connection of Three-phase Four-wire Type Terminal
During operation, do not operate voltage selector switch. Voltage
selection during operation may cause abnormal voltage on the load
side to damage the load and may cause a fire.
In addition it could cause damage to generator and automatic
voltage regulator (AVR).
Be sure to shut off generator before using voltage selector switch.
When voltage selection is completed, lock the voltage selector
switch in position to prevent anyone from operating it.
NOTE; When the voltage selector switch is in the single-phase 240/120V position, place the ammeter
change-over switch to the L1 or L3 position to read the output.
A040189-1
Switch panel for
switching on/off load
A040141
A040251
A040161
A040250
A040153-1
A040154-1
A040155-1
A040156-1
A040157-1
A040158-1
A040159-11
A040160-1
Never use voltage selector switch during operation
480/277V
240/139V
240/120V
Discount-Equipment.com
Summary of Contents for SDG40S-8B1
Page 1: ... www discount equipment com D i s c o u n t E q u i p m e n t c o m ...
Page 63: ...8 Specifications 8 4 Unit mm A100398 D i s c o u n t E q u i p m e n t c o m ...
Page 66: ...D i s c o u n t E q u i p m e n t c o m ...
Page 67: ...10 Piping Diagram 10 1 10 1 Fuel piping A100427E D i s c o u n t E q u i p m e n t c o m ...