background image

termainal of the switch. The input terminal of the
switch should be connected to 5 Amp. fused +24
VDC. The cable clamp strain relief should be used to
secure the field wires.
    3.06.3  The switch should be mounted at a
convenient location in a listed outlet box with
approved strain relief.
        3.06.4 

NOTE: A remote switch, if installed, will

operate only if the local On/Off switch on the face
of the U.P.S. is turned "On".  You may use several
switches or relays in parallel in lieu of one remote
switch.
  3.07  Remote Temperature Sense
    3.07.1
  

CAUTION:  Failure to connect the

remote temperature sense probe correctly will result
in  improper battery charging.
       3.07.2 A 10 foot long cable with temperature
sense probe is provided with the unit.  This allows the
unit to know the exact battery temperature for
correct operation of the temperature compensated
circuitry.  This changes the output voltage as re-
quired by the battery at a given temperature.

3.07.3 Install the probe end on a NEGATIVE

battery terminal post.
          3.08  120 VAC Output (120/240 VAC with
"D" option)

3.08.1  

CAUTION: Do not connect another

source of AC power directly to the output of the
U.P.S. This will result in damage to the inverter that
is not covered under warranty!
      3.08.2 The 120 VAC output of the U.P.S. is
provided at the receptacle outlet on the inverter.
        3.08.3 The output is also presented
behind the wiring compartment panel  for direct
hardwire wire leads.  The black wire is hot (2 black
hot wires with "D" option), the white wire is neutral
and the green wire is ground. The cable clamp strain
relief should be used to secure the field wires.
      3.08.4  The remote AC outlets should be
mounted at a convenient location in a listed outlet
box with approved strain relief.

   3.09  120 VAC Input (120/240 VAC with "D"
option)

   3.09.1 120 VAC (120/240 VAC with "D"

option), 60HZ power from the electric utility or
generator can be connected to the U.P.S. with
hardwire connections at the AC Input wire leads
provided in the hardwire compartment.  The  black
wire is hot (2 black hot wires with "D" option), the
white wire is neutral, and the green wire is ground.
The cable clamp strain relief should be used to
secure the field wires.

    3.09.2  The input circuit should have 20

amp circuit protection from the distribution panel.

   3.09.3  When external AC is supplied, the

internal transfer switch is automatically activated,
the inverter is turned “Off”,  and  the
U.P.S. loads will operate from external AC input.

   3.09.4 The unit has a separate 120 VAC

(240 VAC with "D" option), 20 amp second input
circuit.  The first circuit activates the internal transfer
switch supplying utility or generator power to the
U.P.S. output loads, and turns “Off” the inverter. The
second circuit activates the battery charger and also
turns “Off” the inverter  Both the transfer switch
input and the battery charger input must be at the
same phase.

Page 4

  inverter.

Summary of Contents for ADI-24/2400N

Page 1: ...pply External Battery Type OWNERS MANUAL for Models ADI 24 2400N UPS ADI 24 4800N UPS Including Option D Form 121585 121585B OWNER S MANUAL FEBRUARY 2007 Airpax Dimensions Inc 4467 White Bear Parkway...

Page 2: ...AUTION The U P S contains a circuit breaker and capacitor that may produce a spark Do not mount in a confined battery or gas compartment CAUTION Working in the vicinity of lead acid batteriesisdangero...

Page 3: ...ollowing instructions should be thor oughly read and understood before installation 3 02 CAUTION The U P S produces hazardous voltages to avoid risk of harm or fire the unit must be properly installed...

Page 4: ...put is also presented behind the wiring compartment panel for direct hardwire wire leads The black wire is hot 2 black hot wires with D option the white wire is neutral and the green wire is ground Th...

Page 5: ...tached to the inverter Use the following table to determinecorrectsetting BATTERY CAPACITY SELECTOR SETTING AMP HOUR CAPACITY A Over 600 B 600 400 C 400 200 D Less than 200 4 05 To operate the U P S t...

Page 6: ...ernalcircuitbreakersorfuses b The green Timer Complete light indicates theunit sbatterychargerwasunabletocompletely charge the batteries during the 12 hour charge cycle One or more of the following co...

Page 7: ...NPUT EARTH GROUND EARTH GROUND WARNING CONNECTING THE BATTERY WITH THE WRONG POLARITY TO THE U P S WILL CAUSE DAMAGE THAT IS NOT COVERED UNDER THE WAR RANTY FIG 1 INSTALLATION WIRING FUSE FUSE 24 FROM...

Page 8: ...r for use that the goods or any component thereof manufactured by Dimensions will be free from defects in workmanship for a period of 1 year from the date of purchase provided such goods are installed...

Reviews: