I. GENERAL INFORMATION

INTRODUCTION:
The primary application of the ADI UPS system is to power PLC’s (Program-

mable Logic Controllers), weighing systems, strobe lighting and other elec-
tronic equipment/controls for steel manufacturing plants. The UPS changes the
available 250 volt DC buss to 60 cycle AC power and is a no-break or
uninterruptible system. As the DC input to the UPS has brief outages, the AC
output will remain on uninterrupted. This is accomplished by means of an inter-

nal battery which backs-up the input buss. Steel mills and smelters present an
especially hostile environment to electronic equipment, with high levels of air-
borne particulates, temperature extremes, vibration/mechanical shock, and
high voltage spikes on the 250 volt buss.
The ADI system utilizes patented construction methods, high energy transient

voltage input  protection, and an aluminum NEMA 4X enclosure.

SPECIFICATIONS: ADI-250/900UPS

Output Power- 900 Watts continuous.
DC Input- 190 to 300V, 250 nominal at up to 5 Amperes.
AC Output- 120V, 60Hz +0.05% quasi sine-wave at up to 7.5 Amps.
Efficiency of Conversion- up to 80%.
Operating Temperature- 0

0

 to 40

 C (32

0

 to 104

0

 F).

Transient Surge Protection- will hold a high input voltage pulse to less
than 600V with 200 Amperes flowing for 100 u seconds-370 watt-
seconds peak.
Battery hold-up time- 10 minutes at full load.
Battery recharge time- 5 hours.

Battery float voltage- 27.6VDC @ 20

C.

Enclosure- 24"W x 24"H x 8"D continuous hinge aluminum NEMA type
4X with swing-out internal control panel.
Weight- 80 LBS. excluding batteries.

FEATURES:

PROTECTION:
Converter Low Input Voltage- 5 second surge delay and shutdown at
190VDC with audio alert; auto reset at 205VDC; AC output continues

until Inverter Low Input Voltage shutdown  (low battery).
Overload- 5 second surge delay and shutdown; manual reset by toggle
of on/off switch.
High Temperature- Automatic shutdown protects semiconductors and
transformers; auto reset.

24V Battery- internal 125A fuse.
AC Output- control panel mounted 20A breaker.

Page 4 of 8

Summary of Contents for ADI-250/900UPS

Page 1: ...Inc Uninterruptible Power System OWNERS MANUAL for Model ADI 250 900UPS 121175B Form 121175 OWNERS MANUAL JANUARY 2007 Airpax Dimensions Inc 4467 White Bear Parkway 651 653 7000 St Paul MN 55110 7626...

Page 2: ...S 3 I GENERAL INFORMATION 4 INTRODUCTION SPECIFICATIONS FEATURES II INSTALLATION 5 MOUNTING WIRING III OPERATING INSTRUCTIONS 6 NORMAL OPERATION 250 VOLT BUSS FAILURE IV PRINCIPLES OF OPERATION 7 BLOC...

Page 3: ...ternal disconnect switch After installation and proper operation keep the internal status door closed to protect personnel from dangerous internal voltages Although this unit uses a sealed battery exp...

Page 4: ...I 250 900UPS Output Power 900 Watts continuous DC Input 190 to 300V 250 nominal at up to 5 Amperes AC Output 120V 60Hz 0 05 quasi sine wave at up to 7 5 Amps Efficiency of Conversion up to 80 Operatin...

Page 5: ...ximum temperature The published optimum float voltage at 200 C 680 F is 2 3V cell When temperature changes the float voltage must change This relationship is specified as 3 3mV degree C An example wou...

Page 6: ...age to spec Close door using all door clamps 250VDC BUSS FAILURE If this condition continues beyond a need for UPS power disengage the internal switch until such time when the buss is stable This will...

Page 7: ...wer to the DC to AC power inverter BATTERY Backs up the converter to provide power to the inverter for no break short term power INVERTER Changes the low DC voltage to AC voltage at 60 cycle for outpu...

Page 8: ...Inc extends the following warranty to the original purchaser of those goods subject to the qualifications indicated Dimensions warrants to the original purchaser for use that the goods or any compone...