27
P3
36 YA
#
YA
##
Start of manipulated variable limiting
0,0 … 100,0
0.0
%
37 YE
#
YE
##
End of manipulated variable limiting
0,0 … 100,0
100.0
%
38 YDIR
#
YDIR
Direction of manipulated variable for
display
Rising
Falling
RISE
FALL
RISE
39 YCDO
#
YCDO
Value for Quick Close / bottom
OFF
0,0 … 49,9
0.5
%
40 YCUP
#
YCUP
Value for Quick Close / top
OFF
50,1 … 100,0
99.5
%
41 YNRM
#
YNRM
Standardization of manipulated
variable
MPOS: mechanical travel
FLOW: to flow
MPOS
FLOW
MPOS
P4
42 SAFE
#
SAFE
safe position:
OFF
Freeze
Close
Settings
Open
OFF
KEEP
CLOSE
0,1 … 99,9
OPEN
OFF
%
43 BIN
#
BIN
#
Digital input function:
Enable to activate the "safe
position" function
ON
OFF
OFF
44 DO1
#
DO1
#
Digital output function:
Fault alarm
Fault + non-AUTO
Fault + non-AUTO+BIN
Less than setting value
Higher than setting value
FAULT
FNA
FNAB
LSET
HSET
FAULT
45 SW1
#
SW1
#
Setting value
0,0 … 100,0
0.0
%
46 DO2
#
DO2
#
Digital output function:
Auto/Manual
Less than setting value
Higher than setting value
A/M
LSET
HSET
A/M
47 SW2
#
SW2
#
Setting value
0,0 … 100,0
0.0
%
48 Amin
#
AMIN
Min. output current
4,0 … 20,0
4.0
mA
49 Amax
#
AMAX
Max output current
4,0 ... 20,0
20.0
mA
50 ADIR
#
ADIR
Current output direction
RISE
FALL
RISE
51 PROT
#
PROT
Write protection for HART
ON
OFF
OFF