12
7. Installation details
7.1 Wrench torque sheet for installation
Outside diameter
Torque
mm
inch
Kgf.m
Ф9.52
3/8
4.2
Ф16.0
5/8
6.6
7.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Grade
Unit
9K
12K
18K
24K
mm
2
1.5
1.5
2.5
2.5
7.3 Pipe length and the elevation
Pipe size
Capacity
Btu/h
Gas
Liquid
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
24K
5/8’’ (Ф16.0)
3/8’’ (Ф9.52)
5
10
25
30
Caution:
Capacity is base on standard length and maximum allowance length is base of reliability.
Oil trap should be installed per 5-7 meters.
7.4 Air purging of the piping and indoor unit
Required tools:
Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak detector.
Note:
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration piping, it will affect the
compressor, reduce the cooling capacity, and could lead to a malfunction of unit.
Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas
Summary of Contents for ISM-H24CODC
Page 9: ...6 3 Dimension 3 1 Indoor Unit ISM H24CODC...
Page 10: ...7 3 2 Outdoor Unit ISM H24CODC...
Page 12: ...9 5 Refrigerant cycle diagram...
Page 13: ...10 6 Wiring diagram 6 1 Indoor Unit ISM H24CODC...
Page 14: ...11 6 2 Outdoor Unit ISM H24CODC...
Page 26: ...23 8 6 4 Horizontal louver action is the same as that in cooling mode...