background image

Further Settings can be altered in the /config of the controller or factory settings screen but should be 
done 

with proper testing

 as the results will influence the MAU performance at a fundamental level. 

Making a screenshot (picture) or note of the standard values is a good idea before you adjust these core 
response values. Luckily a “reset to defaults” button exists within the factory settings screen to save the 
day.

To access the Factory Settings page make sure the MUA unit is on and connected to the network router via 
Cat-5 cable. Open a web browser on any device that is connected to the same network as the MUA unit. In 
the URL Address Bar of the browser, type in the IP Address of the MUA Unit and allow the window to load. 
(See

 Network Set-Up

 and it’s “tip” if it does not work)

If the page loads and the MUA interface is up enter (click in it) the address bar and at the end of the IP 
address add /config and press enter, like: 192.168.10.3

/config

The Factory Settings page should now be up. Note: the 6 Bars with numbers in them below the Serial  
Number Bar on the RH side of the page those are the fundamental controls mentioned earlier.

The following fundamental response values for Make-Up Air and Hot Water Heat Control can be adjusted:

Proportional gain:

 The proportional gain determines the ratio of output response to the error signal. For 

instance, if the error term has a magnitude of 10, a proportional gain of 5 would produce a proportional 
response of 50. In general, increasing the proportional gain will increase the speed of the control system 
response.

Integral gain:

 The integral gain controls how much of the Control Output is generated due to the 

accumulated Position Error or Velocity Error while in position control or velocity control, respectively. The 
integral gain units are: percent of the maximum Control Output per unit of control (position, velocity, 
pressure, force etc) of Position Error times time. A low gain slows the response of the axis to changes and 
may keep the axis from reaching the Command Position or Command Velocity. A gain that is too high may 
make the axis oscillate. 

Derivative gain:

 The derivative gain (rate of change) represents the damping effects on the system, 

working with proportional gain to reduce overshoot and oscillations. The term “derivative” is used because 
this parameter is proportional to the rate of change (derivative) of the error. Large derivative action tends 
to destabilize a loop because it doesn't allow it to change. The rule of thumb is that if your derivative time 
is greater than the reset time of your controller, you've got issues. 

NOTE: the “SUBMIT” button must be pushed for the values to be set

PROPER TESTING WITH ALL AIR EXPELLING SOURCES AND MAKE-UP AIR FUNCTIONS PURCHASED MUST BE 
COMPLETED TO VERIFY CORRECT AND EFFICIENT FUNCTIONING OF THE MAKE-UP AIR SYSTEM AND IT’S 
OTHER MODES.

© AirScape MUA-IOM, July 2022, All Rights Reserved.          

         

 

 23

 

          

IN

D

E

X

Summary of Contents for Make-Up Air Unit

Page 1: ...Make Up Air Unit Installation and Operation Manual AirScape MUA IOM July 2022 All Rights Reserved 1 Thank you for your purchase...

Page 2: ...ING ASSIST OPTION INSTALLATION OF THE WHOLE HOUSE FAN OPTION INSTALLATION OF THE HOT WATER HEAT OPTION INSTALLATION OF THE FILTER PRESSURE SENSOR OPTION INSTALLATION OF WIRING AND CONTROL CONTROLLER I...

Page 3: ...s consequences doors open with difficulty and slam shut dirt debris and insects are sucked into the home pilot lights operate erratically fireplaces wood stoves and combustion appliances backdraft and...

Page 4: ...p Air Unit can be determined by reading the differential pressure over the filters This unlocked function also shows up in the graph tab and over time you ll know when to change the filters with real...

Page 5: ...ire electrical shock or injury The fan may come on at any time based on control sequence requirements Never operate the Whole House Fan mode without a window or door opened SUPPLIES INCLUDED Prior to...

Page 6: ...l and duct and or adapter and 18 flex duct Two standard electrical sockets single 15A Hood and Fire Interlock dry contacts and wiring not incl Conduit to run low voltage wiring Coil Box requires a hot...

Page 7: ...Outside Air IN Recirc Air IN Air Inlet Selector Module AIS 2 Heat Assist Recirc Air IN Attic Air IN MUA Controller 10 ft Power Cord Cat5 Fan Cable 10 ft Configuration 3 MAKE UP AIR UNIT WITH Fan Modu...

Page 8: ...re sensor harness and mounting hardware is installed into the controller box The additional software abilities are unlocked in the software config It furthermore requires 1 8 I D Vinyl tubing to conne...

Page 9: ...ted from prevailing winds Select a measuring point outside the house that is sheltered from prevailing winds and reflects the outside pressure without interference as much as possible The attic can be...

Page 10: ...similar to B0 D5 CC 41 98 4F The MAC vendor will show up as Texas Instruments or Beagle Bone The device you are using to interface with must be on the same network you are attempting to access So if y...

Page 11: ...The module is designed to be quickly clicked onto the another module with brackets guiding plates and quick lock clips For this to be done with ease the entire unit has to be removed to create access...

Page 12: ...the MUA unit In the URL Address Bar of the browser type in the IP Address of the MUA Unit and allow the window to load See Network Set Up and it s tip if it does not work If the page loads and the MU...

Page 13: ...e done with ease the entire unit has to be removed to create access and allow you to lock the brackets see image into the other module while you hold the new module at an angle It might be possible to...

Page 14: ...onfig The Factory Settings page should now be up On the right hand bottom of the page there are some check boxes see image Click the Whole House Fan Module check box Click the Submit Button this compl...

Page 15: ...you inspect an already assembled module The Coil Module can be mounted in multiple orientations to fit your needs After you have physically installed the Module you will have to make a few changes to...

Page 16: ...at experts airscapefans com or consult a professional IN PARTICULAR IT IS CRITICAL TO AVOID CONTAMINATING DOMESTIC WATER SYSTEMS In order to activate and control the Hot Water Heat Module added abilit...

Page 17: ...d manually without having to wait for Make Up air conditions also see Start Up and Operation INSTALLATION OF THE FILTER PRESSURE SENSOR OPTION IF YOU PURCHASED YOUR UNIT WITH THIS OPTION THE MAKE UP A...

Page 18: ...n RH Top see image You can also click in the IP Address in the URL Address Bar and by simply deleting the config portion of the address and by pressing Enter you reactivate the main interface It furth...

Page 19: ...s P5 1 to P5 2 all dampers to default Fan OFF Overrides all other modes Safety Interlock KITCHEN HOOD Hood Interlock if triggered connect P5 3 to P5 4 Force Enable Make up Air mode maintains at least...

Page 20: ...options Environmental Status giving you feedback on the measured values there Is more below this but this has been omitted to simplify the amount of information available here TIPS many combinations...

Page 21: ...he building pressure also pressure set point The up to three live temperature readings 3 if you purchased the Heat Assist Option The differential pressure over the filters high pressures or indicates...

Page 22: ...sts the amount of fresh air taken in in IAQ mode The Make up Fan Shutoff Setpoint sets at what speed the fan shuts off The Water Heating Target slider allows you to adjust the temperature you want the...

Page 23: ...nce if the error term has a magnitude of 10 a proportional gain of 5 would produce a proportional response of 50 In general increasing the proportional gain will increase the speed of the control syst...

Page 24: ...e Sensor is connected P12 16 18 20 i2C BUS 1 Usually this is where the Filter Differential Pressure Sensor is connected J1 OAT Outside Air Temperature Sensor connects here J3 IAT Inside Air or Conditi...

Page 25: ...ke up Air when an Appliance such as the Kitchen Hood is activated This will override ALL other active MUA modes EXCEPT the Fire Interlock It is important that no voltage be sent to the board from exte...

Page 26: ...promote an even replacement of air throughout the home and greater the cooling effect Locate this fan at the highest point possible to exploit natural convection and help exhaust the hottest indoor ai...

Page 27: ...x 0 13 1 33 ft2 Round soffit 10 diameter 3 14 x 5 x 5 144 0 55 ft2 50 0 55 ft2 x 0 50 0 28 ft2 Total Net Free Ventilation Area 1 57 ft2 START UP AND OPERATION Note to the user The Airscape Make Up Air...

Page 28: ...doors and windows are closed If so note the current Building Pressure and set the Depressurization Limit slightly above this level The fan speed will increase until the building pressure reaches the M...

Page 29: ...oing so can excessively depressurize your home Only operate your whole house fan mode when the outdoor air temperature is cooler than the indoor temperature Make sure your air conditioner and furnace...

Page 30: ...nia Energy Commision CF Cabinet Fan A module which has a motor driving a fan which moves the air through the system CFM Cubic Feet per Minute An indication of the volume of the air flowing moved by th...

Page 31: ...n to not start Use another cable to rule out a cable issue before proceeding A re settable circuit breaker is located on the Fan mounted electrical box to protect circuit boards from power surges In t...

Page 32: ...66 448 4187 or by email at experts airscapefans com for further assistance NOTE You will be asked for a Serial number for the Fan and Damper Door Box so our technician is able to direct you and or dia...

Page 33: ...um construction with steel inner braces and corner mounts Access panel on one side Insulation R Value R 4 3 Fiberglass Air Inlet Selector AIS AIS Actuator 24VDC 6VA with directional switch and molex A...

Page 34: ...or Evaporator Coil Box Option Condition the incoming Make Up Air with this coil box The controller will throttle the feed to it to achieve targeted temperatures Heating Assist Option Recapture the He...

Page 35: ...AIS Heating Assist Module AIS ROUTER with WIFI Mobile Phone Tablet not incl Inside Air Temp Sensor Mount in Exhaust Air Stream for best response Outside Air Temp Sensor Mount in outside air inlet for...

Reviews: