7
UVHEALTH BIO2000 Installation Manual
4.0 SIZING AND SELECTING UNITS
To maximise the efficiency of your system, it is important
to select the right combination of UVHealth Products.
The UVHealth BIO2000 can be used as a single unit or
in combination with one or more UVHealth BIO1000 or
BIO2000 units. The following table can be used to select
the correct number of units for your application.
Ducted AC Fan Capacity, L/s
750
1000
1500
1750
2000
2250
2500
2750
3000
No. of
BIO1000
req’d
1
0
2
1
0
3
2
1
0
plus
No. of
BIO2000
req’d
0
1
0
1
2
0
1
2
3
Approx
coverage,
m
2
150
200
300
350
400
450
500
550
600
Figure 3 : UVHealth BIO1000 and BIO2000 size selection chart.
Figure 4: UVHealth BIO1000 and BIO2000 application selection chart.
Contaminant Type
Power Supply
Bacteria
Mould
Viruses
VOCs
Odours
24V DC
120 /
230VAC
BIO1000
�
�
�
�
BIO2000
�
�
�
�
�
�
•
For applications with multiple systems, we recommend
a minimum of one unit per system.
•
For larger applications, multiple units are
recommended.
•
Each unit will require its own transformer / power
supply.