8
UVHEALTH BIO2000 Installation Manual
5.0 UVHEALTH BIO2000 INSTALLATION
INSTRUCTIONS
5.1
LAMP INSTALLATION
Disconnect power to all equipment before
beginning this installation. Refer to all warning and
cautionary statements as given in the included
main installation instructions.
Note:
•
The UVHealth BIO2000 installation is specific to
direction of airflow and must be properly positioned
when choosing upflow, downflow, or horizontal
airflow applications. Pay attention to directional
airflow arrow for proper installation.
•
The installation of the UVHealth BIO2000 may be
on the return air side, supply air side, or adjacent the
coil in the supply plenum of the HVAC system.
•
DO NOT locate the UVHealth BIO2000 within 76mm
(direct exposure) of non-UV-C rated flexible ducting,
plastic materials or air filters. UV-C radiation will
degrade many plastic materials over time with direct
exposure. The UVHealth BIO2000 is designed to be
installed on indoor HVAC forced air ducted systems.
•
DO NOT install outdoors. Product is not designed to
be exposed to outdoor elements.
1. The ballast is factory set to 120 Volt AC. Make sure that
the voltage is set to 230 Volt AC by sliding the voltage
selector switch in Figure 5 to the 230 Volt position.
The plug must be replaced, and wiring must be done to
applicable electrical codes.
Figure 5: Location of the voltage selector switch on the ballast
2. Remove the front electrical cover from the unit.
3.. Do not touch the bulb lamp glass section with bare
hands. Wear oil-free cotton type gloves when handling
the glass bulb.
4. Remove the lamp from the packaging and slide non-
pinned end through grommet.
5. Loosen lamp clip and insert lamp so that the end of the
lamp is inside the unit.
6. Tighten lamp clip using the brass knurl. Make sure the
lamp clip tightens around the plastic part of the lamp
and not the glass. See Figure 6.
Figure 6: Location of lamp clip with brass knurl
7. Connect ballast to the four pins on the lamp using the
connector. See Figure 7.
Figure 7: Inserting the four pin connector from the ballast
onto the lamp
8. Wipe down the lamp with the supplied alcohol wipe.