Dampers

  Most dampers are opened and closed automatically via actuator with signal provided 

by the controller, however some may be manually operated via a lifting handle at the 
side of the damper.

 

 

Fans

 

Fan switches on the front of the control panel have 3 settings: Auto, Off and Test. 

 
 

Auto

’ will enable the fans when there is a demand from the controller, which may be 

set via BACnet or local timeclock, dependent upon the controls configuration. This is 

the normal mode of operation. 

 
 

Off

’ will disable the fans so long as other criteria is satisfied (such as a electric 

heater fan run-on operation has been completed, and inverters, if applicable, are set 

to automatic mode). To ensure the fans will not run during a maintenance routine, 
they must be isolated using the main fan isolators mounted on the exterior of the 
unit in the section where the fans are physically located. If the fans are operated via 
inverters, it is recommended to switch off the main isolator to the unit before using 

the fan isolators to prevent the inverters recording a fault and requiring a reset. 

 
 

Test

’ is for air balancing purposes only. Each unit may have a different 

configuration. However, generally, ‘Test’ mode will fully open any fresh air and 

extract dampers, fully close any recirc dampers and run the fans at a speed which 
can be set by a speed potentiometer connected the control panel, an inverter control 
pad, or through a software setting which can be set via touchscreen if applicable. It 
is not recommended to run the unit in ‘Test’ mode, other than for air balancing 

purposes, otherwise the unit will not operate correctly. 

 

Inverters

  Fan inverters can be controlled via a control pad installed inside the control panel 

interior, if applicable. Generally, there is a control pad for each fan. However, in some 

cases, several fans may be run from one control pad. 

 
 

Auto

’ will enable the fan when a signal is received from the controller and run at 

speeds determined by a combination of the settings in the inverter and a control 

signal. This is the normal mode of operation. 

 
 

Hand

’ will run the fan at the speed set on the control pad, which is a frequency in 

Hz, limited by the settings. This can be manually changed using the up and down 

arrows on the keypad to speed up and slow down the fan accordingly. This can be 
useful for air balancing purposes. 

 
 

Off

’ disables the fan. 

 
 

There may be occasions when a fault is shown on the inverter control pad. If you 
notice a fault on the inverter, make a note of the fault code and message. 

 

 

The most common fault occurs when power to the fans is isolated before the 
inverters are isolated. The fan will not run until the fault is reset on the control pad. 
This can be rectified by restoring power to the fans by switching the isolator back on, 
then pushing the ‘Reset’ button on the control pad when the fault is active. If the 

fault does not reset, it may be necessary to turn off power to the main isolator, then 
turn it back on again. 

 
 

For all other inverter faults, please refer to the ABB manual. 

Summary of Contents for CustomAir

Page 1: ... OPERATION MAINTENANCE INSTRUCTIONS Custo Air Handling Units Email TempAir AirSource Heatpumps INSTALLATION OPERATION MAINTENANCE INSTRUCTIONS CustomAir Air Handling Units Tel 0161 425 8553 Fax 0161 637 0232 Email info air source net TempAir AirSource Heatpumps ...

Page 2: ...Maintenance 15 WARRANTY DELIVERY INSTALLATION General COMMISSIONING TESTING MAINTENANCE HEALTH SAFETY General Cautionary Notes Water treatment 3 3 3 Heating Cooling Coils 12 Invalidation of Warranty 3 8 Electrical Connections 8 Ductwork Connections Procedure 2 2 Safety symbols 3 7 Assembly of Multiple Sections 8 Motor Wiring Diagrams 9 Pipework Connections 9 Water Coils Steam Coils DX Coils 10 Con...

Page 3: ...s checks may be required to be carried out prior to our engineer s attendance at site A purchase order number in the event that the fault is not covered under the terms of the warranty An engineer will be scheduled to attend at the earliest availability to carry out an inspection repair of the fault reported Our response will depend on the availability of an engineer and the parts required to carr...

Page 4: ... the hazards that could be encountered when any work is carried out on the equipment for which this manual is written Therefore the following points should be observed to avoid any injuries or health hazards The installation of the unit shall be checked to ensure that A suitable electrical supply is connected Prior to entry to any section please ensure that the electrical supply isolated either at...

Page 5: ...ance Manual oints Longer straps will reduce the sideways force applied to the roof and help prevent damage to the unit Use of spreader beams is recommended to prevent damage to the sides of the AHU Use of spreader beams is recommended to the AHU all straps chains should be vertical during lift IMPORTANT Ensure the forks extend beyond the casing of the unit Upon receipt of equipment a visual inspec...

Page 6: ... stationary for too long periods The balls and races may suffer damage by fretting corrosion false brinelling stationary vibration or static vibration marking Belts Pulleys Wedge belts should be removed from the pulleys and hung up and not exposed to excessive heat or cold and kept free from dampness Belt life is reduced over a long period of non use due to the curing and static condition of rubbe...

Page 7: ...ommend an additional distance equal to the unit dth before any obstacle to prevent recirculation of the exhaust air into the fresh air All units must be installed in accordance with good engineering standards upright level on a prepared base Fixing down of air handling units is at the discretion of the installer and dependant of the site conditions Flexible connections are NOT recommended for conn...

Page 8: ...the unit using sash clamps or ratchet straps chains using the internal corner plates to aid alignment One section should slot into the other CAUTION Before drawing together ensure nothing will get trapped in the space between each section Once the unit has been pulled er install assembly bolts through the corner fixing plates on the inside of the unit For each corner tighten the bolts ensuring goo...

Page 9: ...rate the AHU casework ensure that the casework is adequately sealed to prevent air leakage water ingress If the unit is provided with package controls then always use the cable entry as provided USE THE CORRECT WIRING DIAGRAM AS DETAILED BELOW TO SUIT THE INCOMING MAINS VOLTAGE FAILURE TO DO SO MAY RESULT IN PERMANENT DAMAGE TO THE MOTOR CONTROL GEAR When inverters are provided fitted to the AHU t...

Page 10: ...lters are also Coils are normally designed as either cartridge arrangement where they are fitted inside the casework of the air handling unit or bolted directly between two sections of the AHU All LPHW and chilled water coils are fitted with an air vent and drain plug on the All cooling coils include a condensate drain tray fitted with a drain connection to be connected to an appropriate trapping ...

Page 11: ...g supply lines to the motor to change direction if required Set the inverter frequency as indicated on the HU general arrangement drawing AHU the following checks should be made Refer to General Arrangement drawing for specific details Isolate electric supply to f before entering the fan section Check for any visible damage to the fan impeller and mounting assembly vibration mountings are level an...

Page 12: ...rol panel an inverter control pad or through a software setting which can be set via touchscreen if applicable It is not recommended to run the unit in Test mode other than for air balancing purposes otherwise the unit will not operate correctly Inverters Fan inverters can be controlled via a control pad installed inside the control panel interior if applicable Generally there is a control pad for...

Page 13: ...environment number of hours run but should not be more than three monthly intervals On fans operating in dusty atmospheres or exposed to weather will need to be inspected and cleaned every 3 months If a fan is stationary for long periods in a humid atmosphere it should be switched on minimum of two hours every month to remove any moisture that may have condensed within the motor These should be wi...

Page 14: ...o the rotor surface In situations where self cleaning is not sufficient dependant on the degree of fouling the rotary wheel can be periodically cleaned with compressed air or high pressure water room temperature water only belt is designated SPZ or SPA and is commercially supplied with the belt Connection is done by flexible links Due to the fact that belt is subject to natural stretching which ma...

Page 15: ...ved through the access door by simply sliding the filter out along the channel runner as shown below unlocking before removal To remove gently turn the screw grips as shown highlighted in the red box above at the top of the bag filter anti clockwise then when the screw has been loosened enough twist the locking mechanism horizontally to allow room for the bag filter to be removed with ease Filters...

Page 16: ...s shared by the end user and the appointed maintenance engineers Failure to comply with the F Gas regulations will result in invalidation of the warranty on the refrigeration system within the unit Safety Warning Ensure that all power to the unit is switched off before carrying out any servicing or maintenance task Only trained and qualified service personnel should repair or service air condition...

Page 17: ...cks should be carried out Check the suction and discharge pressures using a service gauge manifold and compare them with the commissioning sheet If there is any significant variation then the fault should be found and corrected Refer to the troubleshooting chart If on inspection of the refrigeration pressures a refrigerant leak is suspected open all access panels to ensure the gas has dissipated t...

Page 18: ...icable in order to reduce risk of frost It is also advisable to close all control valves then switch off any recirculating pumps followed by closing all fresh water and manual valves Small empty spaces suffer from a risk of frost so it is a good idea to blow compressed air through them if available until they are free from residue Allow the fan to run until all surfaces are dry Switch off the main...

Page 19: ...oved by loosening the fixings as per the normal maintenance process then recycled Panel filters are comprised of paper cardboard synthetic felt polymer and steel wire frame Bag filters have a steel frame with felt polymer comprising the main body of the filter and thus must be additionally separated into individual components for most recycling centres Refrigeration Refrigeration circuits MUST be ...

Page 20: ...ely recyclable some sensors such as gas sensors and pressure transducers may contain circuit boards which must be disposed of according to the WEEE Waste Electrical and Electronic Equipment directive inside Europe or relevant RoHS directives Control panel Within the United Kingdom and Europe the majority of electronic components within the control panel will be required to be sent to an accredited...

Reviews: