background image

 

 

 

 

Installation, Operation & Maintenance Manual 

fgfgffhfgfggbffgfV11:0212212121 

 

 

 

All units must be installed in accordance with good engineering standards, upright and 
level on a prepared base. Fixing down of air handling units is at the discretion of the 
installer and dependant of the site conditions. 
Flexible connections are NOT recommended for connecting ductwork to the unit, as the 
fan outlet is fitted with a flexible connector and is isolated from the unit via anti-vibration 
mounts. 
Provision must be made for a cleanable drain trap which should terminate at an open 
drain or tundish which will ensure any blockage can be seen and remedied. 
Units that are delivered in sections should be carefully checked with the general 
arrangement drawings to ensure erection in the correct sequence and handing. The 
sections would be bolted together using the fixing strips, screws and sealing strip 
provided. 
 
 

Electrical  
Installation   

Site wiring must not penetrate or restrict opening or removal of access panels 
 
 
 
Before mounting unit in position it is advisable that consideration is given to the access 
requirements of the unit, particularly with reference to the following : That provision is 
made in the plant room or wherever the unit is to be installed for access to remove the 
following components : 
 

  Fans 

  Electric Heater Batteries 

  Filters (bags or panels) 

  Coils and Pipe work 

 
 

 

 

 

 

Access space is also essential for service and maintenance purposes  

 

 

 

 

 

and for the removal of the motor(s). 

 
 

 
 
 
 
 
 
 
 
 
 
 
 

Storage 

 

 

 

MAINTENANCE OF EQUIPMENT HELD IN STORAGE FOR A PERIOD OF UP TO 2 YEARS 

 
 

Interior 

If ducting is not connected it is essential that all inlets and 

 

discharge openings are completely sealed 

 

 

Exterior 

The  exterior  shall  be  kept  free  from  falling  building  materials, 

 

dampness  or  extreme  cold  or  heat.  The  unit  exterior  surfaces 

 

should  be  inspected  on  a  monthly  basis  and  any  sign  of 

 

corrosion or scratches are to be treated immediately. 

 
 

Static 

Machines  fitted  with  ball  bearings  may  be  damaged  if  left 

Indentation

 

stationary for too long

 

 

 

periods.  The  balls  and  races  may  suffer  damage  by  fretting 

 

corrosion  (false  brinelling,  stationary  vibration  or  static  vibration 

 

marking). 

 
 

Belts & Pulleys 

Wedge belts should be removed from the pulleys and hung up and 

 

not  exposed  to  excessive  heat  or  cold  and  kept  free  from 

 

dampness. Belt life is reduced over a long period of non-use due to 

 

the curing and static condition  of  rubber.  Pulleys  already  taper-

 

locked to shafts can be lightly covered with rustproof compound. 

 

This must be thoroughly cleaned off prior to start up. 

 
 

Filters 

All filters, whether in the form of bags or panels, must be suitably 

 

wrapped  and  sealed  to  prevent  damp  and  ingress  of  dust  or 

 

foreign bodies, and held in a dry store. 

 
 

Fan Shaft 

During the interval between delivery and commissioning the drive 

Bearings

 

belts  should  be  slackened  and  the  fan  and  motor  shafts  rotated 

 

one  quarter  of  a  revolution  at  intervals  of  once  a  week.  Bearings 

 

fitted with shields should not be stored for periods exceeding two 

 

(2) years since the grease ages. Bearings stored for longer periods 

 

than that specified may  be found  to have  a higher initial  starting 

 

torque and the service life of the grease will then be   shortened. 

 

It is therefore advisable to repack the grease after twelve months 

 

of  non  use.  Fan  shafts  and  impellers  should  be  protected  with 

 

rustproof compound to prevent any corrosion taking place. 

 
 

Electric Motors 

Clean  out  all  the  dust  accumulated  inside  and  outside  the  motor 

 

and  make  sure  that  all  the  component  parts  of  the  motor  are  in 

 

good condition. Cover   all the ventilating holes on the motor frame 

 

to prevent dust from entering   the motor. Apply a coating of anti-

 

corrosion grease or other anti-corrosion agent on all the parts that 

 

may  be  subject  to  rusting.  Care  must  be  taken  to  see  that  the 

 

storeroom  is  always  dry  and  well  ventilated  while  the  room 

 

temperature  is  regularly  maintained  above  0°C.  During  storage, 

 

periodic inspections should be made to check for moisture, rust or 

 

hardening of grease.  

 

 

The  above  are  intended  to  preserve  the  life  of  all  static  and 
moving parts of the equipment during the period of storage. It 
is  advisable  that  regular  attention  of  the  equipment  is 
maintained. 

 

Summary of Contents for CustomAir

Page 1: ... OPERATION MAINTENANCE INSTRUCTIONS Custo Air Handling Units Email TempAir AirSource Heatpumps INSTALLATION OPERATION MAINTENANCE INSTRUCTIONS CustomAir Air Handling Units Tel 0161 425 8553 Fax 0161 637 0232 Email info air source net TempAir AirSource Heatpumps ...

Page 2: ...Maintenance 15 WARRANTY DELIVERY INSTALLATION General COMMISSIONING TESTING MAINTENANCE HEALTH SAFETY General Cautionary Notes Water treatment 3 3 3 Heating Cooling Coils 12 Invalidation of Warranty 3 8 Electrical Connections 8 Ductwork Connections Procedure 2 2 Safety symbols 3 7 Assembly of Multiple Sections 8 Motor Wiring Diagrams 9 Pipework Connections 9 Water Coils Steam Coils DX Coils 10 Con...

Page 3: ...s checks may be required to be carried out prior to our engineer s attendance at site A purchase order number in the event that the fault is not covered under the terms of the warranty An engineer will be scheduled to attend at the earliest availability to carry out an inspection repair of the fault reported Our response will depend on the availability of an engineer and the parts required to carr...

Page 4: ... the hazards that could be encountered when any work is carried out on the equipment for which this manual is written Therefore the following points should be observed to avoid any injuries or health hazards The installation of the unit shall be checked to ensure that A suitable electrical supply is connected Prior to entry to any section please ensure that the electrical supply isolated either at...

Page 5: ...ance Manual oints Longer straps will reduce the sideways force applied to the roof and help prevent damage to the unit Use of spreader beams is recommended to prevent damage to the sides of the AHU Use of spreader beams is recommended to the AHU all straps chains should be vertical during lift IMPORTANT Ensure the forks extend beyond the casing of the unit Upon receipt of equipment a visual inspec...

Page 6: ... stationary for too long periods The balls and races may suffer damage by fretting corrosion false brinelling stationary vibration or static vibration marking Belts Pulleys Wedge belts should be removed from the pulleys and hung up and not exposed to excessive heat or cold and kept free from dampness Belt life is reduced over a long period of non use due to the curing and static condition of rubbe...

Page 7: ...ommend an additional distance equal to the unit dth before any obstacle to prevent recirculation of the exhaust air into the fresh air All units must be installed in accordance with good engineering standards upright level on a prepared base Fixing down of air handling units is at the discretion of the installer and dependant of the site conditions Flexible connections are NOT recommended for conn...

Page 8: ...the unit using sash clamps or ratchet straps chains using the internal corner plates to aid alignment One section should slot into the other CAUTION Before drawing together ensure nothing will get trapped in the space between each section Once the unit has been pulled er install assembly bolts through the corner fixing plates on the inside of the unit For each corner tighten the bolts ensuring goo...

Page 9: ...rate the AHU casework ensure that the casework is adequately sealed to prevent air leakage water ingress If the unit is provided with package controls then always use the cable entry as provided USE THE CORRECT WIRING DIAGRAM AS DETAILED BELOW TO SUIT THE INCOMING MAINS VOLTAGE FAILURE TO DO SO MAY RESULT IN PERMANENT DAMAGE TO THE MOTOR CONTROL GEAR When inverters are provided fitted to the AHU t...

Page 10: ...lters are also Coils are normally designed as either cartridge arrangement where they are fitted inside the casework of the air handling unit or bolted directly between two sections of the AHU All LPHW and chilled water coils are fitted with an air vent and drain plug on the All cooling coils include a condensate drain tray fitted with a drain connection to be connected to an appropriate trapping ...

Page 11: ...g supply lines to the motor to change direction if required Set the inverter frequency as indicated on the HU general arrangement drawing AHU the following checks should be made Refer to General Arrangement drawing for specific details Isolate electric supply to f before entering the fan section Check for any visible damage to the fan impeller and mounting assembly vibration mountings are level an...

Page 12: ...rol panel an inverter control pad or through a software setting which can be set via touchscreen if applicable It is not recommended to run the unit in Test mode other than for air balancing purposes otherwise the unit will not operate correctly Inverters Fan inverters can be controlled via a control pad installed inside the control panel interior if applicable Generally there is a control pad for...

Page 13: ...environment number of hours run but should not be more than three monthly intervals On fans operating in dusty atmospheres or exposed to weather will need to be inspected and cleaned every 3 months If a fan is stationary for long periods in a humid atmosphere it should be switched on minimum of two hours every month to remove any moisture that may have condensed within the motor These should be wi...

Page 14: ...o the rotor surface In situations where self cleaning is not sufficient dependant on the degree of fouling the rotary wheel can be periodically cleaned with compressed air or high pressure water room temperature water only belt is designated SPZ or SPA and is commercially supplied with the belt Connection is done by flexible links Due to the fact that belt is subject to natural stretching which ma...

Page 15: ...ved through the access door by simply sliding the filter out along the channel runner as shown below unlocking before removal To remove gently turn the screw grips as shown highlighted in the red box above at the top of the bag filter anti clockwise then when the screw has been loosened enough twist the locking mechanism horizontally to allow room for the bag filter to be removed with ease Filters...

Page 16: ...s shared by the end user and the appointed maintenance engineers Failure to comply with the F Gas regulations will result in invalidation of the warranty on the refrigeration system within the unit Safety Warning Ensure that all power to the unit is switched off before carrying out any servicing or maintenance task Only trained and qualified service personnel should repair or service air condition...

Page 17: ...cks should be carried out Check the suction and discharge pressures using a service gauge manifold and compare them with the commissioning sheet If there is any significant variation then the fault should be found and corrected Refer to the troubleshooting chart If on inspection of the refrigeration pressures a refrigerant leak is suspected open all access panels to ensure the gas has dissipated t...

Page 18: ...icable in order to reduce risk of frost It is also advisable to close all control valves then switch off any recirculating pumps followed by closing all fresh water and manual valves Small empty spaces suffer from a risk of frost so it is a good idea to blow compressed air through them if available until they are free from residue Allow the fan to run until all surfaces are dry Switch off the main...

Page 19: ...oved by loosening the fixings as per the normal maintenance process then recycled Panel filters are comprised of paper cardboard synthetic felt polymer and steel wire frame Bag filters have a steel frame with felt polymer comprising the main body of the filter and thus must be additionally separated into individual components for most recycling centres Refrigeration Refrigeration circuits MUST be ...

Page 20: ...ely recyclable some sensors such as gas sensors and pressure transducers may contain circuit boards which must be disposed of according to the WEEE Waste Electrical and Electronic Equipment directive inside Europe or relevant RoHS directives Control panel Within the United Kingdom and Europe the majority of electronic components within the control panel will be required to be sent to an accredited...

Reviews:

Related manuals for CustomAir