PERFORMANCE DATA & PRESSURE CURVES
5-1
SM TELECOM 1-A.0 GB
5. PERFORMANCE
DATA
5.1
SX 12 TELECOM / GC 12 LT R410A
5.1.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OU COIL (°C)
DATA
ENTERING AIR WB/DB ID COIL ( °C)
15/21
17/24
19/27
21/29
23/32
15
(1)
TC
3.64
3.86
4.03
4.21
4.36
SC
2.48 2.63
2.78
2.71
2.76
PI
0.75
0.75
0.75
0.76
0.76
20
(1)
TC
3.61 3.82
4.00
4.18
4.32
SC
2.57 2.73
2.89
2.80
2.86
PI
0.81 0.82
0.82
0.83
0.83
25
TC
3.46 3.71
3.93
4.11
4.25
SC
2.42
2.59
2.74
2.69
2.76
PI
0.88 0.89
0.89
0.90
0.90
30
TC
3.25
3.50
3.78
3.93
4.07
SC
2.29 2.48
2.68
2.62
2.73
PI
0.95 0.96
0.97
0.98
0.98
35
TC
3.00
3.25
3.57
3.75
3.89
SC
2.16 2.35
2.57
2.54
2.64
PI
1.03
1.04
1.06
1.07
1.07
40
TC
2.71 2.96
3.28
3.46
3.61
SC
2.01
2.21
2.43
2.39
2.51
PI
1.11 1.12
1.14
1.16
1.16
46
TC
2.36
2.61
2.93
3.11
3.25
SC
1.83 2.02
2.28
2.24
2.34
PI
1.21
1.23
1.26
1.27
1.28
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OU –
Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
CONTENTS
Summary of Contents for GC 12 LT
Page 13: ...OUTLINE DIMENSIONS 4 3 SM TELECOM 1 A 0 GB 4 5 Outdoor Unit GC 30T LT CONTENTS...
Page 28: ...CONTROL SYSTEM 11 3 SM TELECOM 1 A 0 GB 11 1 4 Main PCB Controller CONTENTS...
Page 70: ...EXPLODED VIEWS SPARE PARTS LISTS 13 6 SM TELECOM 1 A 0 GB 13 6 Outdoor Unit GC 12 LT CONTENTS...
Page 72: ...EXPLODED VIEWS SPARE PARTS LISTS 13 8 SM TELECOM 1 A 0 GB 13 8 Outdoor Unit GC 18 LT CONTENTS...
Page 87: ...APPENDIX A 15 1 SM TELECOM 1 A 0 GB APPENDIX A INSTALLATION AND OPERATION MANUAL CONTENTS...