PERFORMANCE DATA & PRESSURE CURVES
5-4
SM TELECOM 1-A.0 GB
5.5
Capacity Correction Factor Due to Tubing Length
5.5.1 Cooling
TOTAL TUBING LENGTH
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.02
1
0.990
0.975
0.960 0.945
---
---
---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
5.6 Pressure
Curves
5.6.1 Cooling
Discharge Pressure VS.Outdoor Temp
10.0
20.0
30.0
40.0
15
20
25
30
35
40
46
Outdoor Temp.(
o
C DB)
Discharge Pressure(Bar)
15/21(WB/DB)
17/24(WB/DB)
19/27(WB/DB)
21/29(WB/DB)
23/32(WB/DB)
Suction Pressure VS.Outdoor Temp
5.0
7.0
9.0
11.0
15
20
25
30
35
40
46
Outdoor Temp.(
o
C DB)
Suction Pressure(Bar)
15/21(WB/DB)
17/24(WB/DB)
19/27(WB/DB)
21/29(WB/DB)
23/32(WB/DB)
CONTENTS
Summary of Contents for GC 12 LT
Page 13: ...OUTLINE DIMENSIONS 4 3 SM TELECOM 1 A 0 GB 4 5 Outdoor Unit GC 30T LT CONTENTS...
Page 28: ...CONTROL SYSTEM 11 3 SM TELECOM 1 A 0 GB 11 1 4 Main PCB Controller CONTENTS...
Page 70: ...EXPLODED VIEWS SPARE PARTS LISTS 13 6 SM TELECOM 1 A 0 GB 13 6 Outdoor Unit GC 12 LT CONTENTS...
Page 72: ...EXPLODED VIEWS SPARE PARTS LISTS 13 8 SM TELECOM 1 A 0 GB 13 8 Outdoor Unit GC 18 LT CONTENTS...
Page 87: ...APPENDIX A 15 1 SM TELECOM 1 A 0 GB APPENDIX A INSTALLATION AND OPERATION MANUAL CONTENTS...