CONTROL SYSTEM
11-21
SM TELECOM 1-A.0 GB
b. Auto Cooling or Heating RH Group
Maintains room temp. at desired level by selecting between Cooling or Heating Modes.
(RT - SPT) [
o
c]
+3
+2
+1
0
-1
-2
-3
ON
OFF
ON
OFF
L
OFF
ON
OFF
H/M/L
30 sec
COMP
& OFAN
HE1
HE2
IFAN
RV
OFF
> 3 min
(2)
Auto Heat Mode
Auto Cool Mode
Auto Heat Mode
(1)
> 3 min
(2)
11.11 Dry
Mode
11.11.1
Dry, ST or RC Group or P2000 Model with Any Group Settings
Mode: DRY
Temp: Selected desired temperature
Fan:
LOW (automatically selected by software)
Timer: Any
I-FEEL: Any
Control function
Reduce room humidity with minimum temp. fluctuations by operating in Cool Mode with
LOW speed IFAN.