CONTROL SYSTEM
11-24
SM TELECOM 1-A.0 GB
11.12 Protection
11.12.1
Cooling Mode Protections
a. Indoor
Coil
Defrost
Mode: COOLING,
DRY,
AUTO
Temp:
Selected desired temp.
Fan: Any
Timer: Any
I-FEEL: ON or OFF
Control Function
Protects the indoor coil from ice formation at low ambient temperatures.
ICT [
o
c]
+2
ON
OFF
ON
OFF
t1
t2
t3
COMP
OFAN
+1
+5
+14
0
-1
ON
OFF
IFAN
t1
t1 = 5 min minimum for each COMP starting.
t2 = OFAN cycling (alternate between ON and OFF every 30 sec) for 20 min maximum.
t3 = COMP and OFAN stops for 10 min minimum.