CONTROL SYSTEM
11-35
SM TELECOM 1-A.0 GB
d. STEP 3: AUTO LED WALK TEST.
1) All the LEDS will turn OFF.
2) All the LEDS will turn ON for 1 second one by one in the following sequence:
STAND-BY
Ö
OPERATE
Ö
TIMER
Ö
FILTER
Ö
COOL
Ö
HEAT.
3) In PRX all the LEDS will turn ON for 1 second one by one in the following
sequence : 18 °c
Ö
20 °c
Ö
22 °c
Ö
24 °c
Ö
26 °c
Ö
28 °c
Ö
30 °c
Ö
High IFAN
Ö
Auto IFAN
Ö
Med IFAN
Ö
Low IFAN
Ö
STAND-BY
Ö
TIMER
Ö
FILTER
Ö
COOL
Ö
HEAT.
e. STEP 4: AUTO REALY WALK TEST:
All relays will energize one by one in the following sequence:
COMPRESSOR
Ö
OUTDOOR FAN
Ö
R. V.
Ö
HEATER 1
Ö
HEATER 2
Ö
INDOOR WATER PUMP
Ö
SWING or OUTDOOR WATER PUMP
Ö
INDOOR
FAN: LOW
Ö
MID
Ö
HIGH.
When the relay walk test is completed, the next test will start automatically.
f.
STEP 5: FREQUENCY TESTING:
If the frequency measuring process fails the COOL LED will turn ON. In order to
move to the next step, press ON/OFF button on the remote control.
g. STEP 6: INPUT TEST.
The test purpose is to check the analog real time indicators (thermistors, LEVEL
and clock) according to the table below.
LED Indicator
Condition for LED to be ON
STBY LED
Room thermistor
z
25°c
OPER LED
Indoor coil thermistor
z
25°c
TIMER LED
Outdoor coil thermistor
z
25°c
FILTER LED
Clock
COOL LED
LEVEL 2&3
HEAT LED
LEVEL 4
h. STEP 7: TIMING RESET TEST (WATCH DOG).
The test purpose is to verify that the CPU rise time after power failure is between 1
to 3 sec, test results are indicated on the LEDS : STAND-BY,OPER, TIMER and
FILTER turning ON one by one.
The results of the test are coded as follows:
Pass condition:
1 sec - STAND-BY and OPER are turned ON
2 sec - STAND-BY, OPER and TIMER are turned ON
CONTENTS
Summary of Contents for GC 12 LT
Page 13: ...OUTLINE DIMENSIONS 4 3 SM TELECOM 1 A 0 GB 4 5 Outdoor Unit GC 30T LT CONTENTS...
Page 28: ...CONTROL SYSTEM 11 3 SM TELECOM 1 A 0 GB 11 1 4 Main PCB Controller CONTENTS...
Page 70: ...EXPLODED VIEWS SPARE PARTS LISTS 13 6 SM TELECOM 1 A 0 GB 13 6 Outdoor Unit GC 12 LT CONTENTS...
Page 72: ...EXPLODED VIEWS SPARE PARTS LISTS 13 8 SM TELECOM 1 A 0 GB 13 8 Outdoor Unit GC 18 LT CONTENTS...
Page 87: ...APPENDIX A 15 1 SM TELECOM 1 A 0 GB APPENDIX A INSTALLATION AND OPERATION MANUAL CONTENTS...