CONTROL SYSTEM
11-37
SM TELECOM 1-A.0 GB
11.16 System
Diagnostics
Pressing Mode button for 5-10 seconds in SB or any other operation mode will activate
the DIAGNOSTICS mode, acknowledged by 3 short beeps and lighting of COOL and
HEAT LEDs.
In DIAGNOSTICS mode, system failures will be indicated by the blinking of HEAT &
COOL LEDs.
The coding method is as follows:
x
HEAT LED blinks 5 times in 5 seconds, and then turns off for the next 5
seconds.
x
COOL LED blinks during the same 5 seconds according to the following table:
No.
Problem
1 2 3 4 5
1
RT1 is disconnected
ż
Ɣ
Ɣ
Ɣ
Ɣ
2
RT1 is shorted
ż
Ɣ
Ɣ
Ɣ
ż
3 RV
fault
ż
Ɣ
Ɣ
ż
Ɣ
4
RT2 is disconnected
Ɣ
ż
Ɣ
Ɣ
Ɣ
5
RT2 is shorted
Ɣ
ż
Ɣ
Ɣ
ż
6 (Reserved)
Ɣ
ż
Ɣ
ż
Ɣ
7
RT2 temp reading doesn’t change
Ɣ
ż
Ɣ
ż
ż
8
RT3 is disconnected
Ɣ
Ɣ
ż
Ɣ
Ɣ
9
RT3 is shorted
Ɣ
Ɣ
ż
Ɣ
ż
10 (Reserved)
Ɣ
Ɣ
ż
ż
Ɣ
11
RT3 temp reading doesn’t change
Ɣ
Ɣ
ż
ż
ż
12
RT2 & RT3 temp reading doesn’t change
Ɣ
ż
ż
ż
ż
LEGEND
ż
- ON,
Ɣ
- OFF
NOTES
1. If faults occur in more than one thermistor (except case
number 12 in table above), only one fault will be indicated
according to the following order: RT3, RT2, RT1.
2. A/C will return to normal mode when sending a command by
the R/C during system DIAGNOSTICS mode. If the command
from the R/C contains a Group ID, the ID will become the new
Group ID of the ELCON unit.
CONTENTS
Summary of Contents for GC 12 LT
Page 13: ...OUTLINE DIMENSIONS 4 3 SM TELECOM 1 A 0 GB 4 5 Outdoor Unit GC 30T LT CONTENTS...
Page 28: ...CONTROL SYSTEM 11 3 SM TELECOM 1 A 0 GB 11 1 4 Main PCB Controller CONTENTS...
Page 70: ...EXPLODED VIEWS SPARE PARTS LISTS 13 6 SM TELECOM 1 A 0 GB 13 6 Outdoor Unit GC 12 LT CONTENTS...
Page 72: ...EXPLODED VIEWS SPARE PARTS LISTS 13 8 SM TELECOM 1 A 0 GB 13 8 Outdoor Unit GC 18 LT CONTENTS...
Page 87: ...APPENDIX A 15 1 SM TELECOM 1 A 0 GB APPENDIX A INSTALLATION AND OPERATION MANUAL CONTENTS...